Product Program Category |
Uninterruptible Power Supplies |
Uninterruptible Power Supplies |
Type |
Ac-output UPS |
Ac-output UPS |
Brand Name |
APC by Schneider Electric |
APC by Schneider Electric |
Model Name |
APC Back UPS Pro BX1500M Compact Tower 1500VA AVR LCD 120V |
Smart-UPS Online 1000VA RM NC TAA |
Model Number |
BX1500M |
SRT1000RMXLA-NCUS |
UPC |
731,304,331,780 |
731304329978 |
CB Model Identifier |
ES_22220_BX1500M_07292018110050_2050313 |
ES_22220_SRT1000RMXLA-NCUS_103020232033487_3502142 |
Meets ENERGY STAR Most Efficient 2024 Criteria |
No |
No |
ENERGY STAR Partner |
Schneider Electric |
Schneider Electric |
Product Category |
Uninterruptible Power Supplies |
Uninterruptible Power Supplies |
Additional Model Information |
APC Back UPS Pro BX1500M Compact Tower 1500VA AVR LCD 120V Factory Serviced,BX1500MW,; Std Exch APC Back UPS Pro BX1500M Compact Tower 1500VA AVR LCD 120V,BX1500MQ, |
N/A |
Date Available On Market |
January 1, 2019 |
January 22, 2024 |
Date Certified |
July 16, 2018 |
October 31, 2023 |
Markets |
United States |
United States |
Power Conversion Mechanism |
Static |
Static |
Minimum Configuration Tested Model Number |
BX1500M |
SRT1000RMXLA-NC |
Active Output Power Rating Minimum Configuration (W) |
900 |
900 |
Apparent Output Power Rating Minimum Configuration (VA) |
1,500 |
1000 |
Topology (ac) |
Line Interactive |
Multi-Mode Double Conversion |
Topology and Product Type Combined |
ac Line Interactive (VI) |
ac - Other |
Application |
Consumer |
Commercial |
Rated Input Voltage (V rms) |
120-120 |
120-120 |
Rated Input Frequency (Hz) |
60-60 |
50-60 |
Rated Output Voltage (V) |
120-120 |
120-120 |
Rated Output Frequency (Hz) |
60-60 |
50-60 |
Rack Mountable |
No |
Yes |
Height (mm) |
250 |
85 |
Width (mm) |
100 |
432 |
Depth (mm) |
382 |
508 |
Total Number of Outlets |
10 |
6 |
Number of Battery Backup and Surge Protected Outlets |
5 |
6 |
Number of Surge Protected Only Outlets |
5 |
0 |
Normal Mode(s) Input Dependency Characteristic (ac) |
Voltage and Frequency Dependent |
Voltage and Frequency Independent,Voltage and Frequency Dependent |
Modular UPS |
No |
No |
Number of Normal Modes |
Single-normal-mode |
Multiple-normal-mode |
Default Normal Mode (ac) |
Voltage and Frequency Dependent |
Voltage and Frequency Independent |
Test Input Voltage (V rms) |
120 |
120 |
Test Input Frequency (Hz) |
60 |
60 |
Test Output Voltage (V) |
120 |
120 |
Test Output Frequency (Hz) |
60 |
60 |
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac) |
3 |
35.92 |
Efficiency at 25% Load Min Config Lowest Dependency (ac) |
99 |
84.3 |
Efficiency at 50% Load Min Config Lowest Dependency (ac) |
99 |
89.9 |
Efficiency at 75% Load Min Config Lowest Dependency (ac) |
99 |
91.6 |
Efficiency at 100% Load Min Config Lowest Dependency (ac) |
99 |
92.3 |
Weighted Efficiency Calc Min Config Lowest Dependency |
99 |
91.3 |
Minimum Configuration Input Power Factor Lowest-Input Dependency |
1 |
0.98 |
Efficiency (%) |
99 |
91.3 |
Modular UPS Module Tested Model Number |
N/A |
N/A |
Energy Storage Mechanism |
Battery |
Battery |
Energy Storage System Technology |
Valve Regulated Lead-acid Battery |
Valve Regulated Lead-acid Battery |
Energy Storage System Configuration |
Integral |
Integral |
Energy Storage System Removable to Another Room |
N/A |
No |
Energy Storage System Runtime at 100% Load (min.) |
3 |
11 |
Energy Storage System Runtime at 50% Load (min.) |
11 |
25 |
Energy Storage System Warranty (yrs) |
2 |
2 |
Energy Storage System Information URL |
http://www.apc.com/shop/us/en/products/P-APCRBC124 |
http://www.apc.com/shop/us/en/products/P-APCRBC155 |
Battery Recycling URL |
http://www.apc.com/us/en/who-we-are/sustainability/recycling-options.jsp |
https://www.apc.com/us/en/who-we-are/sustainability/recycling-options.jsp |
Network Connections Available |
USB Port |
Serial Port,Ethernet,USB Port |
Communication Protocols |
Other |
HTTP,HTTPS,Other,Modbus TCP,Modbus RTU |
Communication Protocol Other |
USB Power Summary |
USB Power Summary, Micro-Link, Simple Signaling,SNMP (v1, 2 or 3) |
Manufacturer Take Back Program |
Yes |
Yes |
Manufacturer Take Back Program URL |
http://www.apc.com/us/en/who-we-are/sustainability/recycling-options.jsp |
http://www.apc.com/company/us/en/sustainability/recycling-options/ |
Model Web Page URL |
http://www.apc.com/shop/us/en/products/P-BX1500M |
https://www.apc.com/us/en/product-category/88972-uninterruptible-power-supply-ups/ |
Test Method Guidelines |
http://www.apc.com/us/en/who-we-are/sustainability/ |
http://www.apc.com/company/us/en/sustainability/energy-efficiency/ |
Date Qualified |
July 16, 2018 |
October 31, 2023 |