Compare CyberPower – CP825LCDa vs CyberPower – PR5000LCDRTXL5U Specifications

CP825LCDa PR5000LCDRTXL5U
ENERGY STAR Partner
Cyber Power Systems, Inc. Cyber Power Systems, Inc.
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
CyberPower CyberPower
Model Name
CP825LCDa PR5000LCDRTXL5U
Model Number
CP825LCDa PR5000LCDRTXL5U
Additional Model Information
CP600LCDa,CP600LCDa, PR5000LCDRTXL5UN,PR5000LCDRTXL5UN,; PR5000LCDRTXL5UNTAA,PR5000LCDRTXL5UNTAA,; PR5000LCDRTXL5UTAA,PR5000LCDRTXL5UTAA,
Date Available On Market
September 1, 2018 March 31, 2016
Date Certified
August 22, 2018 January 14, 2019
Markets
United States, Canada United States, Canada
CB Model Identifier
ES_1095904_CP825LCDa_08232018110527_2327669 ES_1095904_PR5000LCDRTXL5U_02212019082529_7529417
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
CP825LCDa PR5000LCDRTXL2U
Active Output Power Rating Minimum Configuration (W)
450 4500
Apparent Output Power Rating Minimum Configuration (VA)
850 5000
Topology (ac)
Passive Standby Line Interactive
Topology and Product Type Combined
Alternating Current (ac) - Offline (VFD) ac Line Interactive (VI)
Application
Consumer Commercial,Consumer,Data Center
Rated Input Voltage (V rms)
120-120 208-240
Rated Input Frequency (Hz)
60-60 50-60
Rated Output Voltage (V)
120-120 208-240
Rated Output Frequency (Hz)
60-60 50-60
Rack Mountable
Yes Yes
Rack Mount Height (U)
2 5
Height (mm)
169 433
Width (mm)
88 220
Depth (mm)
28 645
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage and Frequency Dependent Voltage Independent
Modular UPS
No No
Number of Normal Modes
Single-normal-mode Single-normal-mode
Default Normal Mode (ac)
Voltage and Frequency Dependent Voltage Independent
Test Input Voltage (V rms)
120 230
Test Input Frequency (Hz)
60 50
Test Output Voltage (V)
120 230
Test Output Frequency (Hz)
60 50
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
3 5.4
Efficiency at 25% Load Min Config Lowest Dependency (ac)
97 98.8
Efficiency at 50% Load Min Config Lowest Dependency (ac)
98 98.7
Efficiency at 75% Load Min Config Lowest Dependency (ac)
99 98.5
Efficiency at 100% Load Min Config Lowest Dependency (ac)
99 98.3
Weighted Efficiency Calc Min Config Lowest Dependency
98 98.5
Efficiency (%)
98 98.5
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Integral Integral
Energy Storage System Removable to Another Room
No No
Energy Storage System Runtime at 100% Load (min.)
1 10
Energy Storage System Runtime at 50% Load (min.)
14 28
Energy Storage System Warranty (yrs)
3 3
Energy Storage System Information URL
N/A N/A
Network Connections Available
USB Port Serial Port,USB Port,Ethernet
Communication Protocols
None HTTPS,Other,HTTP,SNMP (v1, 2 or 3)
Manufacturer Take Back Program
No Yes
Model Web Page URL
N/A https://www.cyberpowersystems.com/product/ups/pr5000lcdrtxl5u/
Test Method Guidelines
N/A N/A
Date Qualified
August 22, 2018 January 14, 2019

Compare CyberPower - CP825LCDa With Other 105 Models