OL3000RTXL2U CP1500PFCLCDa
ENERGY STAR Partner
Cyber Power Systems, Inc. Cyber Power Systems, Inc.
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
CyberPower CyberPower
Model Name
OL3000RTXL2U CP1500PFCLCDa
Model Number
OL3000RTXL2U CP1500PFCLCDa
Date Available On Market
July 1, 2013 July 31, 2019
Date Certified
September 19, 2018 July 28, 2019
Markets
United States United States, Taiwan, Japan, Canada
CB Model Identifier
ES_1095904_OL3000RTXL2U_09192018083457_6097421 ES_1095904_CP1500PFCLCDa_07292019060200_0120655
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
OL3000RTXL2U CP1350PFCLCDa
Active Output Power Rating Minimum Configuration (W)
2,700 880
Apparent Output Power Rating Minimum Configuration (VA)
3,000 1350
Topology (ac)
Double Conversion Passive Standby
Topology and Product Type Combined
ac - Double Conversion (VFI) Alternating Current (ac) - Offline (VFD)
Application
Commercial,Consumer Consumer,Commercial
Rated Input Voltage (V rms)
100-125 120-120
Rated Input Frequency (Hz)
50-60 60-60
Rated Output Voltage (V)
100-125 120-120
Rated Output Frequency (Hz)
50-60 60-60
Rack Mountable
Yes No
Rack Mount Height (U)
2 N/A
Height (mm)
88 280
Width (mm)
433 100
Depth (mm)
600 354
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage and Frequency Dependent,Voltage and Frequency Independent Voltage Independent
Modular UPS
No No
Number of Normal Modes
Multiple-normal-mode Single-normal-mode
Default Normal Mode (ac)
Voltage and Frequency Independent Voltage Independent
Test Input Voltage (V rms)
120 120
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
120 120
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
47 3.56
Efficiency at 25% Load Min Config Lowest Dependency (ac)
90 98.2
Efficiency at 50% Load Min Config Lowest Dependency (ac)
92 98.8
Efficiency at 75% Load Min Config Lowest Dependency (ac)
92 98.9
Efficiency at 100% Load Min Config Lowest Dependency (ac)
91 98.8
Weighted Efficiency Calc Min Config Lowest Dependency
92 98.8
Efficiency (%)
92 98.8
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Integral Integral
Energy Storage System Removable to Another Room
No No
Energy Storage System Runtime at 100% Load (min.)
4 2
Energy Storage System Runtime at 50% Load (min.)
11 9
Energy Storage System Warranty (yrs)
3 3
Energy Storage System Information URL
http://www.cyberpowersystems.com/ N/A
Network Connections Available
Serial Port,USB Port,Ethernet Serial Port,Ethernet,USB Port
Communication Protocols
HTTPS,HTTP,SNMP (v1, 2 or 3) HTTP,HTTPS,Other,SNMP (v1, 2 or 3)
Manufacturer Take Back Program
Yes No
Model Web Page URL
http://www.cyberpowersystems.com No (Not yet available)
Test Method Guidelines
http://www.cyberpowersystems.com/ N/A
Date Qualified
September 19, 2018 July 28, 2019