ENERGY STAR Partner |
Cyber Power Systems, Inc. |
Cyber Power Systems, Inc. |
Product Category |
Uninterruptible Power Supplies |
Uninterruptible Power Supplies |
Type |
Ac-output UPS |
Ac-output UPS |
Brand Name |
CyberPower |
CyberPower |
Model Name |
OL3000RTXL2U |
CP1500PFCRM2U |
Model Number |
OL3000RTXL2U |
CP1500PFCRM2U |
Date Available On Market |
July 1, 2013 |
March 28, 2022 |
Date Certified |
September 19, 2018 |
January 25, 2022 |
Markets |
United States |
United States, Taiwan, Canada |
CB Model Identifier |
ES_1095904_OL3000RTXL2U_09192018083457_6097421 |
ES_1095904_CP1500PFCRM2U_122820211859868_9245731 |
Meets ENERGY STAR Most Efficient 2024 Criteria |
No |
No |
Power Conversion Mechanism |
Static |
Static |
Minimum Configuration Tested Model Number |
OL3000RTXL2U |
CP1500PFCRM2U |
Active Output Power Rating Minimum Configuration (W) |
2,700 |
1000 |
Apparent Output Power Rating Minimum Configuration (VA) |
3,000 |
1500 |
Topology (ac) |
Double Conversion |
Line Interactive |
Topology and Product Type Combined |
ac - Double Conversion (VFI) |
ac Line Interactive (VI) |
Application |
Commercial,Consumer |
Consumer,Commercial |
Rated Input Voltage (V rms) |
100-125 |
120-120 |
Rated Input Frequency (Hz) |
50-60 |
60-60 |
Rated Output Voltage (V) |
100-125 |
120-120 |
Rated Output Frequency (Hz) |
50-60 |
60-60 |
Rack Mountable |
Yes |
Yes |
Rack Mount Height (U) |
2 |
2 |
Height (mm) |
88 |
433 |
Width (mm) |
433 |
266 |
Depth (mm) |
600 |
86 |
Normal Mode(s) Input Dependency Characteristic (ac) |
Voltage and Frequency Dependent,Voltage and Frequency Independent |
Voltage Independent |
Modular UPS |
No |
No |
Number of Normal Modes |
Multiple-normal-mode |
Single-normal-mode |
Default Normal Mode (ac) |
Voltage and Frequency Independent |
Voltage Independent |
Test Input Voltage (V rms) |
120 |
120 |
Test Input Frequency (Hz) |
60 |
60 |
Test Output Voltage (V) |
120 |
120 |
Test Output Frequency (Hz) |
60 |
60 |
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac) |
47 |
2.94 |
Efficiency at 25% Load Min Config Lowest Dependency (ac) |
90 |
98.5 |
Efficiency at 50% Load Min Config Lowest Dependency (ac) |
92 |
98.9 |
Efficiency at 75% Load Min Config Lowest Dependency (ac) |
92 |
98.9 |
Efficiency at 100% Load Min Config Lowest Dependency (ac) |
91 |
98.7 |
Weighted Efficiency Calc Min Config Lowest Dependency |
92 |
98.8 |
Efficiency (%) |
92 |
98.8 |
Modular UPS Module Tested Model Number |
N/A |
N/A |
Energy Storage Mechanism |
Battery |
Battery |
Energy Storage System Technology |
Valve Regulated Lead-acid Battery |
Valve Regulated Lead-acid Battery |
Energy Storage System Configuration |
Integral |
Integral |
Energy Storage System Removable to Another Room |
No |
No |
Energy Storage System Runtime at 100% Load (min.) |
4 |
2 |
Energy Storage System Runtime at 50% Load (min.) |
11 |
10 |
Energy Storage System Warranty (yrs) |
3 |
1 |
Energy Storage System Information URL |
http://www.cyberpowersystems.com/ |
N/A |
Network Connections Available |
Serial Port,USB Port,Ethernet |
Other,USB Port,Ethernet |
Communication Protocols |
HTTPS,HTTP,SNMP (v1, 2 or 3) |
None |
Manufacturer Take Back Program |
Yes |
No |
Model Web Page URL |
http://www.cyberpowersystems.com |
N/A |
Test Method Guidelines |
http://www.cyberpowersystems.com/ |
N/A |
Date Qualified |
September 19, 2018 |
January 25, 2022 |