Compare CyberPower – OL3000RTXL2U vs CyberPower – PR2000RTXL2U Specifications

OL3000RTXL2U PR2000RTXL2U
ENERGY STAR Partner
Cyber Power Systems, Inc. Cyber Power Systems, Inc.
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
CyberPower CyberPower
Model Name
OL3000RTXL2U PR2000RTXL2U
Model Number
OL3000RTXL2U PR2000RTXL2U
Date Available On Market
July 1, 2013 July 1, 2018
Date Certified
September 19, 2018 June 8, 2018
Markets
United States United States, Taiwan, Japan, Canada
CB Model Identifier
ES_1095904_OL3000RTXL2U_09192018083457_6097421 ES_1095904_PR2000RTXL2U_06212018110131_8891341
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
OL3000RTXL2U PR2000RTXL2U
Active Output Power Rating Minimum Configuration (W)
2,700 2000
Apparent Output Power Rating Minimum Configuration (VA)
3,000 2000
Topology (ac)
Double Conversion Line Interactive
Topology and Product Type Combined
ac - Double Conversion (VFI) ac Line Interactive (VI)
Application
Commercial,Consumer Consumer
Rated Input Voltage (V rms)
100-125 100-125
Rated Input Frequency (Hz)
50-60 50-60
Rated Output Voltage (V)
100-125 100-125
Rated Output Frequency (Hz)
50-60 50-60
Rack Mountable
Yes Yes
Rack Mount Height (U)
2 N/A
Height (mm)
88 87
Width (mm)
433 433
Depth (mm)
600 500
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage and Frequency Dependent,Voltage and Frequency Independent Voltage Independent
Modular UPS
No No
Number of Normal Modes
Multiple-normal-mode Single-normal-mode
Default Normal Mode (ac)
Voltage and Frequency Independent Voltage Independent
Test Input Voltage (V rms)
120 120
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
120 120
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
47 6.37
Efficiency at 25% Load Min Config Lowest Dependency (ac)
90 98.3
Efficiency at 50% Load Min Config Lowest Dependency (ac)
92 98.4
Efficiency at 75% Load Min Config Lowest Dependency (ac)
92 98.1
Efficiency at 100% Load Min Config Lowest Dependency (ac)
91 97.8
Weighted Efficiency Calc Min Config Lowest Dependency
92 98
Efficiency (%)
92 98
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Integral Integral
Energy Storage System Removable to Another Room
No N/A
Energy Storage System Runtime at 100% Load (min.)
4 4
Energy Storage System Runtime at 50% Load (min.)
11 13
Energy Storage System Warranty (yrs)
3 3
Energy Storage System Information URL
http://www.cyberpowersystems.com/ N/A
Network Connections Available
Serial Port,USB Port,Ethernet Serial Port,Ethernet,USB Port
Communication Protocols
HTTPS,HTTP,SNMP (v1, 2 or 3) HTTP,HTTPS,Other,SNMP (v1, 2 or 3)
Manufacturer Take Back Program
Yes Yes
Model Web Page URL
http://www.cyberpowersystems.com N/A
Test Method Guidelines
http://www.cyberpowersystems.com/ N/A
Date Qualified
September 19, 2018 June 8, 2018

Compare CyberPower - OL3000RTXL2U With Other 105 Models