ENERGY STAR Partner |
Cyber Power Systems, Inc. |
Cyber Power Systems, Inc. |
Product Category |
Uninterruptible Power Supplies |
Uninterruptible Power Supplies |
Type |
Ac-output UPS |
Ac-output UPS |
Brand Name |
CyberPower |
CyberPower |
Model Name |
PR1500RTXL2U |
OL8KRTHD |
Model Number |
PR1500RTXL2U |
OL8KRTHD |
Additional Model Information |
PR1000RT2U JP,PR1000RT2U JP,; PR1000RT2U,PR1000RT2U,; PR1000RT2UC,PR1000RT2UC,; PR1000RT2UCN,PR1000RT2UCN,; PR1000RTXL2U JP,PR1000RTXL2U JP,; PR1000RTXL2U,PR1000RTXL2U,; PR1000RTXL2UC,PR1000RTXL2UC,; PR1500RT2U JP,PR1500RT2U JP,; PR1500RT2U,PR1500RT2U,; PR1500RT2UC,PR1500RT2UC,; PR1500RT2UCN,PR1500RT2UCN,; PR1500RTXL2UC JP,PR1500RTXL2UC JP,; PR1500RTXL2UC,PR1500RTXL2UC,; PR1500RTXL2UCN,PR1500RTXL2UCN,; PRL1500RT2UC JP,PRL1500RT2UC JP,; PRL1500RT2UC,PRL1500RT2UC,; PRL1500RT2UCN,PRL1500RT2UCN, |
OL8KRTHDHW,OL8KRTHDHW,; OL8KRTHDHWTW,OL8KRTHDHWTW,; OL8KRTHDIEC,OL8KRTHDIEC,; OL8KRTHDIECTAA,OL8KRTHDIECTAA,; OL8KRTHDIECTW,OL8KRTHDIECTW,; OL8KRTHDS,OL8KRTHDS,; OL8KRTHDSHW,OL8KRTHDSHW,; OL8KRTHDSIEC,OL8KRTHDSIEC,; OL8KRTHDSIECTAA,OL8KRTHDSIECTAA,; OL8KRTHDSTAA,OL8KRTHDSTAA,; OL8KRTHDSTAAHW,OL8KRTHDSTAAHW,; OL8KRTHDTAA,OL8KRTHDTAA,; OL8KRTHDTAAHW,OL8KRTHDTAAHW,; OL8KRTHDTW,OL8KRTHDTW, |
Date Available On Market |
July 1, 2018 |
August 1, 2022 |
Date Certified |
June 8, 2018 |
September 6, 2022 |
Markets |
United States, Taiwan, Japan, Canada |
United States, Canada |
CB Model Identifier |
ES_1095904_PR1500RTXL2U_06212018104839_8119638 |
ES_1123345_OL8KRTHD_081720220954877_4706831 |
Meets ENERGY STAR Most Efficient 2024 Criteria |
No |
No |
Power Conversion Mechanism |
Static |
Static |
Minimum Configuration Tested Model Number |
PRL1500RTXL2U |
OL8KRTHD |
Active Output Power Rating Minimum Configuration (W) |
1,500 |
8000 |
Apparent Output Power Rating Minimum Configuration (VA) |
1,500 |
8000 |
Topology (ac) |
Line Interactive |
Double Conversion |
Topology and Product Type Combined |
ac Line Interactive (VI) |
ac - Double Conversion (VFI) |
Application |
Consumer |
Data Center,Consumer,Commercial |
Rated Input Voltage (V rms) |
100-125 |
200-240 |
Rated Input Frequency (Hz) |
50-60 |
50-60 |
Rated Output Voltage (V) |
100-125 |
200-240 |
Rated Output Frequency (Hz) |
50-60 |
50-60 |
Rack Mountable |
Yes |
Yes |
Height (mm) |
87 |
173 |
Width (mm) |
433 |
433 |
Depth (mm) |
500 |
720 |
Normal Mode(s) Input Dependency Characteristic (ac) |
Voltage Independent |
Voltage and Frequency Independent,Voltage and Frequency Dependent |
Modular UPS |
No |
No |
Number of Normal Modes |
Single-normal-mode |
Multiple-normal-mode |
Default Normal Mode (ac) |
Voltage Independent |
Voltage and Frequency Independent |
Test Input Voltage (V rms) |
120 |
240 |
Test Input Frequency (Hz) |
60 |
60 |
Test Output Voltage (V) |
120 |
240 |
Test Output Frequency (Hz) |
60 |
60 |
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac) |
4 |
22.21 |
Efficiency at 25% Load Min Config Lowest Dependency (ac) |
98 |
93.5 |
Efficiency at 50% Load Min Config Lowest Dependency (ac) |
99 |
94.6 |
Efficiency at 75% Load Min Config Lowest Dependency (ac) |
99 |
94.7 |
Efficiency at 100% Load Min Config Lowest Dependency (ac) |
98 |
94.5 |
Weighted Efficiency Calc Min Config Lowest Dependency |
99 |
94.6 |
Efficiency (%) |
99 |
94.6 |
Modular UPS Module Tested Model Number |
N/A |
N/A |
Energy Storage Mechanism |
Battery |
Battery |
Energy Storage System Technology |
Valve Regulated Lead-acid Battery |
Valve Regulated Lead-acid Battery |
Energy Storage System Configuration |
Integral |
Integral |
Energy Storage System Removable to Another Room |
N/A |
No |
Energy Storage System Runtime at 100% Load (min.) |
7 |
2 |
Energy Storage System Runtime at 50% Load (min.) |
19 |
7 |
Energy Storage System Warranty (yrs) |
3 |
3 |
Energy Storage System Information URL |
N/A |
N/A |
Network Connections Available |
Serial Port,Ethernet,USB Port |
Serial Port,Other,USB Port |
Communication Protocols |
HTTP,HTTPS,Other,SNMP (v1, 2 or 3) |
HTTP,HTTPS,SNMP (v1, 2 or 3) |
Communication Protocol Other |
TCP/IP, UDP |
N/A |
Manufacturer Take Back Program |
Yes |
Yes |
Model Web Page URL |
N/A |
http://www.cyberpowersystems.com/ |
Test Method Guidelines |
N/A |
N/A |
Date Qualified |
June 8, 2018 |
September 6, 2022 |