Compare CyberPower – PR2000RTXL2U vs CyberPower – OL3000RTXL2UN Specifications

PR2000RTXL2U OL3000RTXL2UN
ENERGY STAR Partner
Cyber Power Systems, Inc. Cyber Power Systems, Inc.
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
CyberPower CyberPower
Model Name
PR2000RTXL2U OL3000RTXL2UN
Model Number
PR2000RTXL2U OL3000RTXL2UN
Additional Model Information
PR2000RT2U JP,PR2000RT2U JP,; PR2000RT2U,PR2000RT2U,; PR2000RT2UC,PR2000RT2UC,; PR2000RT2UCN,PR2000RT2UCN,; PR2000RTXL2UC,PR2000RTXL2UC,; PR2000RTXL2UCN,PR2000RTXL2UCN, N/A
Date Available On Market
July 1, 2018 July 1, 2013
Date Certified
June 8, 2018 September 19, 2018
Markets
United States, Taiwan, Japan, Canada United States
CB Model Identifier
ES_1095904_PR2000RTXL2U_06212018110131_8891341 ES_1095904_OL3000RTXL2UN_09192018083824_6304201
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
PR2000RTXL2U OL3000RTXL2U
Active Output Power Rating Minimum Configuration (W)
2,000 2700
Apparent Output Power Rating Minimum Configuration (VA)
2,000 3000
Topology (ac)
Line Interactive Double Conversion
Topology and Product Type Combined
ac Line Interactive (VI) ac - Double Conversion (VFI)
Application
Consumer Commercial,Consumer
Rated Input Voltage (V rms)
100-125 100-125
Rated Input Frequency (Hz)
50-60 50-60
Rated Output Voltage (V)
100-125 100-125
Rated Output Frequency (Hz)
50-60 50-60
Rack Mountable
Yes Yes
Height (mm)
87 88
Width (mm)
433 433
Depth (mm)
500 600
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage Independent Voltage and Frequency Dependent,Voltage and Frequency Independent
Modular UPS
No No
Number of Normal Modes
Single-normal-mode Multiple-normal-mode
Default Normal Mode (ac)
Voltage Independent Voltage and Frequency Independent
Test Input Voltage (V rms)
120 120
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
120 120
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
6 46.93
Efficiency at 25% Load Min Config Lowest Dependency (ac)
98 89.8
Efficiency at 50% Load Min Config Lowest Dependency (ac)
98 91.7
Efficiency at 75% Load Min Config Lowest Dependency (ac)
98 91.6
Efficiency at 100% Load Min Config Lowest Dependency (ac)
98 91.2
Weighted Efficiency Calc Min Config Lowest Dependency
98 91.5
Efficiency (%)
98 91.5
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Integral Integral
Energy Storage System Removable to Another Room
N/A No
Energy Storage System Runtime at 100% Load (min.)
4 4
Energy Storage System Runtime at 50% Load (min.)
13 11
Energy Storage System Warranty (yrs)
3 3
Energy Storage System Information URL
N/A http://www.cyberpowersystems.com/
Network Connections Available
Serial Port,Ethernet,USB Port Serial Port,USB Port,Ethernet
Communication Protocols
HTTP,HTTPS,Other,SNMP (v1, 2 or 3) HTTPS,HTTP,SNMP (v1, 2 or 3)
Communication Protocol Other
TCP/IP, UDP N/A
Manufacturer Take Back Program
Yes Yes
Model Web Page URL
N/A http://www.cyberpowersystems.com
Test Method Guidelines
N/A http://www.cyberpowersystems.com/
Date Qualified
June 8, 2018 September 19, 2018

Compare CyberPower - PR2000RTXL2U With Other 105 Models