ENERGY STAR Partner |
Cyber Power Systems, Inc. |
Cyber Power Systems, Inc. |
Product Category |
Uninterruptible Power Supplies |
Uninterruptible Power Supplies |
Type |
Ac-output UPS |
Ac-output UPS |
Brand Name |
CyberPower |
CyberPower |
Model Name |
PR2000RTXL2U |
SL900UC |
Model Number |
PR2000RTXL2U |
SL900UC |
Additional Model Information |
PR2000RT2U JP,PR2000RT2U JP,; PR2000RT2U,PR2000RT2U,; PR2000RT2UC,PR2000RT2UC,; PR2000RT2UCN,PR2000RT2UCN,; PR2000RTXL2UC,PR2000RTXL2UC,; PR2000RTXL2UCN,PR2000RTXL2UCN, |
SL950U,SL950U, |
Date Available On Market |
July 1, 2018 |
April 1, 2024 |
Date Certified |
June 8, 2018 |
January 11, 2024 |
Markets |
United States, Taiwan, Japan, Canada |
United States |
CB Model Identifier |
ES_1095904_PR2000RTXL2U_06212018110131_8891341 |
ES_1095904_SL900UC_011120240823320_1147679 |
Meets ENERGY STAR Most Efficient 2024 Criteria |
No |
No |
Power Conversion Mechanism |
Static |
Static |
Minimum Configuration Tested Model Number |
PR2000RTXL2U |
SL900UC |
Active Output Power Rating Minimum Configuration (W) |
2,000 |
480 |
Apparent Output Power Rating Minimum Configuration (VA) |
2,000 |
900 |
Topology (ac) |
Line Interactive |
Passive Standby |
Topology and Product Type Combined |
ac Line Interactive (VI) |
Alternating Current (ac) - Offline (VFD) |
Application |
Consumer |
Data Center,Consumer,Commercial |
Rated Input Voltage (V rms) |
100-125 |
120-120 |
Rated Input Frequency (Hz) |
50-60 |
50-60 |
Rated Output Voltage (V) |
100-125 |
120-120 |
Rated Output Frequency (Hz) |
50-60 |
50-60 |
Rack Mountable |
Yes |
No |
Height (mm) |
87 |
138 |
Width (mm) |
433 |
324 |
Depth (mm) |
500 |
70 |
Normal Mode(s) Input Dependency Characteristic (ac) |
Voltage Independent |
Voltage and Frequency Dependent |
Modular UPS |
No |
No |
Number of Normal Modes |
Single-normal-mode |
Single-normal-mode |
Default Normal Mode (ac) |
Voltage Independent |
Voltage and Frequency Dependent |
Test Input Voltage (V rms) |
120 |
120 |
Test Input Frequency (Hz) |
60 |
60 |
Test Output Voltage (V) |
120 |
120 |
Test Output Frequency (Hz) |
60 |
60 |
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac) |
6 |
2.12 |
Efficiency at 25% Load Min Config Lowest Dependency (ac) |
98 |
98.1 |
Efficiency at 50% Load Min Config Lowest Dependency (ac) |
98 |
98.8 |
Efficiency at 75% Load Min Config Lowest Dependency (ac) |
98 |
99 |
Efficiency at 100% Load Min Config Lowest Dependency (ac) |
98 |
99 |
Weighted Efficiency Calc Min Config Lowest Dependency |
98 |
98.8 |
Efficiency (%) |
98 |
98.8 |
Modular UPS Module Tested Model Number |
N/A |
N/A |
Energy Storage Mechanism |
Battery |
Battery |
Energy Storage System Technology |
Valve Regulated Lead-acid Battery |
Valve Regulated Lead-acid Battery |
Energy Storage System Configuration |
Integral |
Integral |
Energy Storage System Removable to Another Room |
N/A |
No |
Energy Storage System Runtime at 100% Load (min.) |
4 |
1 |
Energy Storage System Runtime at 50% Load (min.) |
13 |
7 |
Energy Storage System Warranty (yrs) |
3 |
3 |
Energy Storage System Information URL |
N/A |
https://www.cyberpowersystems.com/ |
Network Connections Available |
Serial Port,Ethernet,USB Port |
None |
Communication Protocols |
HTTP,HTTPS,Other,SNMP (v1, 2 or 3) |
None |
Communication Protocol Other |
TCP/IP, UDP |
N/A |
Manufacturer Take Back Program |
Yes |
Yes |
Model Web Page URL |
N/A |
http://www.cyberpowersystems.com/ |
Test Method Guidelines |
N/A |
https://www.cyberpowersystems.com/ |
Date Qualified |
June 8, 2018 |
January 11, 2024 |