ENERGY STAR Partner |
Cyber Power Systems, Inc. |
Cyber Power Systems, Inc. |
Product Category |
Uninterruptible Power Supplies |
Uninterruptible Power Supplies |
Type |
Ac-output UPS |
Ac-output UPS |
Brand Name |
CyberPower |
CyberPower |
Model Name |
PR3000RTXL2UA |
OL3000RTXL2UHV |
Model Number |
PR3000RTXL2UA |
OL3000RTXL2UHV |
Additional Model Information |
PR2200RT2U JP,PR2200RT2U JP,; PR2200RT2U,PR2200RT2U,; PR2200RT2UC,PR2200RT2UC,; PR2200RT2UCN,PR2200RT2UCN,; PR2200RTXL2U JP,PR2200RTXL2U JP,; PR2200RTXL2U,PR2200RTXL2U,; PR2200RTXL2UA JP,PR2200RTXL2UA JP,; PR2200RTXL2UA,PR2200RTXL2UA,; PR2200RTXL2UAC,PR2200RTXL2UAC,; PR2200RTXL2UACN,PR2200RTXL2UACN,; PR2200RTXL2UC,PR2200RTXL2UC,; PR2200RTXL2UCN,PR2200RTXL2UCN,; PR3000RT2U JP,PR3000RT2U JP,; PR3000RT2U,PR3000RT2U,; PR3000RT2UC,PR3000RT2UC,; PR3000RT2UCN,PR3000RT2UCN,; PR3000RTXL2U JP,PR3000RTXL2U JP,; PR3000RTXL2U,PR3000RTXL2U,; PR3000RTXL2UA JP,PR3000RTXL2UA JP,; PR3000RTXL2UAC,PR3000RTXL2UAC,; PR3000RTXL2UACN,PR3000RTXL2UACN,; PR3000RTXL2UC,PR3000RTXL2UC,; PR3000RTXL2UCN,PR3000RTXL2UCN,; PRL3000RT2UC,PRL3000RT2UC,; PRL3000RT2UCN,PRL3000RT2UCN, |
N/A |
Date Available On Market |
August 1, 2018 |
June 10, 2016 |
Date Certified |
January 17, 2023 |
September 19, 2018 |
Markets |
United States, Taiwan, Japan, Canada |
United States |
CB Model Identifier |
ES_1095904_PR3000RTXL2UA_07292018101208_9128733 |
ES_1095904_OL3000RTXL2UHV_09192018081230_4750391 |
Meets ENERGY STAR Most Efficient 2024 Criteria |
No |
No |
Power Conversion Mechanism |
Static |
Static |
Minimum Configuration Tested Model Number |
PR2200RTXL2UA |
OL3000RTXL2UHV |
Active Output Power Rating Minimum Configuration (W) |
2,200 |
2700 |
Apparent Output Power Rating Minimum Configuration (VA) |
2,200 |
3000 |
Maximum Configuration Tested Model Number |
PR3000RTXL2UA |
N/A |
Active Output Power Rating Maximum Configuration (W) |
3,000 |
N/A |
Topology (ac) |
Line Interactive |
Double Conversion |
Topology and Product Type Combined |
ac Line Interactive (VI) |
ac - Double Conversion (VFI) |
Application |
Consumer |
Commercial,Consumer |
Rated Input Voltage (V rms) |
100-120 |
200-240 |
Rated Input Frequency (Hz) |
50-60 |
50-60 |
Rated Output Voltage (V) |
100-120 |
200-240 |
Rated Output Frequency (Hz) |
50-60 |
50-60 |
Rack Mountable |
Yes |
Yes |
Rack Mount Height (U) |
2 |
2 |
Height (mm) |
87 |
88 |
Width (mm) |
433 |
433 |
Depth (mm) |
630 |
600 |
Normal Mode(s) Input Dependency Characteristic (ac) |
Voltage Independent |
Voltage and Frequency Dependent,Voltage and Frequency Independent |
Modular UPS |
No |
No |
Number of Normal Modes |
Single-normal-mode |
Multiple-normal-mode |
Default Normal Mode (ac) |
Voltage Independent |
Voltage and Frequency Independent |
Test Input Voltage (V rms) |
120 |
230 |
Test Input Frequency (Hz) |
60 |
60 |
Test Output Voltage (V) |
120 |
230 |
Test Output Frequency (Hz) |
60 |
60 |
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac) |
4 |
40.76 |
Efficiency at 25% Load Min Config Lowest Dependency (ac) |
98 |
89.4 |
Efficiency at 50% Load Min Config Lowest Dependency (ac) |
98 |
91.7 |
Efficiency at 75% Load Min Config Lowest Dependency (ac) |
98 |
92.1 |
Efficiency at 100% Load Min Config Lowest Dependency (ac) |
98 |
92.1 |
Weighted Efficiency Calc Min Config Lowest Dependency |
98 |
92 |
Total Input Power in W at 0% Load Max Config Lowest Dependency (ac) |
5 |
N/A |
Efficiency at 25% Load Max Config Lowest Dependency (ac) |
99 |
N/A |
Efficiency at 50% Load Max Config Lowest Dependency (ac) |
99 |
N/A |
Efficiency at 75% Load Max Config Lowest Dependency (ac) |
99 |
N/A |
Efficiency at 100% Load Max Config Lowest Dependency (ac) |
98 |
N/A |
Weighted Efficiency Calc Max Config Lowest Dependency |
99 |
N/A |
Efficiency (%) |
98 |
92 |
Modular UPS Module Tested Model Number |
N/A |
N/A |
Energy Storage Mechanism |
Battery |
Battery |
Energy Storage System Technology |
Valve Regulated Lead-acid Battery |
Valve Regulated Lead-acid Battery |
Energy Storage System Configuration |
Integral |
Integral |
Energy Storage System Removable to Another Room |
No |
No |
Energy Storage System Runtime at 100% Load (min.) |
4 |
4 |
Energy Storage System Runtime at 50% Load (min.) |
11 |
11 |
Energy Storage System Warranty (yrs) |
3 |
3 |
Energy Storage System Information URL |
N/A |
http://www.cyberpowersystems.com/ |
Network Connections Available |
Serial Port,Ethernet,USB Port |
Serial Port,USB Port,Ethernet |
Communication Protocols |
HTTP,HTTPS,Other,SNMP (v1, 2 or 3) |
HTTPS,HTTP,SNMP (v1, 2 or 3) |
Communication Protocol Other |
TCP/IP, UDP |
N/A |
Manufacturer Take Back Program |
Yes |
Yes |
Model Web Page URL |
N/A |
http://www.cyberpowersystems.com |
Test Method Guidelines |
N/A |
http://www.cyberpowersystems.com/ |
Date Qualified |
January 17, 2023 |
September 19, 2018 |