Compare CyberPower – PR3000RTXL2UA vs CyberPower – PS1500AVRLCD Specifications

PR3000RTXL2UA PS1500AVRLCD
ENERGY STAR Partner
Cyber Power Systems, Inc. Cyber Power Systems, Inc.
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
CyberPower CyberPower
Model Name
PR3000RTXL2UA PS1500AVRLCD
Model Number
PR3000RTXL2UA PS1500AVRLCD
Additional Model Information
PR2200RT2U JP,PR2200RT2U JP,; PR2200RT2U,PR2200RT2U,; PR2200RT2UC,PR2200RT2UC,; PR2200RT2UCN,PR2200RT2UCN,; PR2200RTXL2U JP,PR2200RTXL2U JP,; PR2200RTXL2U,PR2200RTXL2U,; PR2200RTXL2UA JP,PR2200RTXL2UA JP,; PR2200RTXL2UA,PR2200RTXL2UA,; PR2200RTXL2UAC,PR2200RTXL2UAC,; PR2200RTXL2UACN,PR2200RTXL2UACN,; PR2200RTXL2UC,PR2200RTXL2UC,; PR2200RTXL2UCN,PR2200RTXL2UCN,; PR3000RT2U JP,PR3000RT2U JP,; PR3000RT2U,PR3000RT2U,; PR3000RT2UC,PR3000RT2UC,; PR3000RT2UCN,PR3000RT2UCN,; PR3000RTXL2U JP,PR3000RTXL2U JP,; PR3000RTXL2U,PR3000RTXL2U,; PR3000RTXL2UA JP,PR3000RTXL2UA JP,; PR3000RTXL2UAC,PR3000RTXL2UAC,; PR3000RTXL2UACN,PR3000RTXL2UACN,; PR3000RTXL2UC,PR3000RTXL2UC,; PR3000RTXL2UCN,PR3000RTXL2UCN,; PRL3000RT2UC,PRL3000RT2UC,; PRL3000RT2UCN,PRL3000RT2UCN, N/A
Date Available On Market
August 1, 2018 April 30, 2021
Date Certified
January 17, 2023 June 28, 2021
Markets
United States, Taiwan, Japan, Canada United States, Taiwan, Canada
CB Model Identifier
ES_1095904_PR3000RTXL2UA_07292018101208_9128733 ES_1095904_PS1500AVRLCD_032820222020180_3180118
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
PR2200RTXL2UA CST150UC
Active Output Power Rating Minimum Configuration (W)
2,200 900
Apparent Output Power Rating Minimum Configuration (VA)
2,200 1500
Maximum Configuration Tested Model Number
PR3000RTXL2UA N/A
Active Output Power Rating Maximum Configuration (W)
3,000 N/A
Topology (ac)
Line Interactive Line Interactive
Topology and Product Type Combined
ac Line Interactive (VI) ac Line Interactive (VI)
Application
Consumer Consumer,Commercial
Rated Input Voltage (V rms)
100-120 120-120
Rated Input Frequency (Hz)
50-60 60-60
Rated Output Voltage (V)
100-120 120-120
Rated Output Frequency (Hz)
50-60 60-60
Rack Mountable
Yes No
Rack Mount Height (U)
2 N/A
Height (mm)
87 249
Width (mm)
433 99
Depth (mm)
630 348
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage Independent Voltage Independent
Modular UPS
No No
Number of Normal Modes
Single-normal-mode Single-normal-mode
Default Normal Mode (ac)
Voltage Independent Voltage Independent
Test Input Voltage (V rms)
120 120
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
120 120
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
4 3.3
Efficiency at 25% Load Min Config Lowest Dependency (ac)
98 98.1
Efficiency at 50% Load Min Config Lowest Dependency (ac)
98 98.8
Efficiency at 75% Load Min Config Lowest Dependency (ac)
98 98.9
Efficiency at 100% Load Min Config Lowest Dependency (ac)
98 98.8
Weighted Efficiency Calc Min Config Lowest Dependency
98 98.8
Total Input Power in W at 0% Load Max Config Lowest Dependency (ac)
5 N/A
Efficiency at 25% Load Max Config Lowest Dependency (ac)
99 N/A
Efficiency at 50% Load Max Config Lowest Dependency (ac)
99 N/A
Efficiency at 75% Load Max Config Lowest Dependency (ac)
99 N/A
Efficiency at 100% Load Max Config Lowest Dependency (ac)
98 N/A
Weighted Efficiency Calc Max Config Lowest Dependency
99 N/A
Efficiency (%)
98 98.8
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Integral Integral
Energy Storage System Removable to Another Room
No No
Energy Storage System Runtime at 100% Load (min.)
4 3
Energy Storage System Runtime at 50% Load (min.)
11 11
Energy Storage System Warranty (yrs)
3 3
Energy Storage System Information URL
N/A N/A
Network Connections Available
Serial Port,Ethernet,USB Port Other,USB Port,Ethernet
Communication Protocols
HTTP,HTTPS,Other,SNMP (v1, 2 or 3) None
Communication Protocol Other
TCP/IP, UDP N/A
Manufacturer Take Back Program
Yes No
Model Web Page URL
N/A N/A
Test Method Guidelines
N/A N/A
Date Qualified
January 17, 2023 June 28, 2021