Compare CyberPower – PR3000RTXL2UA vs CyberPower – SE450G1 Specifications

PR3000RTXL2UA SE450G1
ENERGY STAR Partner
Cyber Power Systems, Inc. Cyber Power Systems, Inc.
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
CyberPower CyberPower
Model Name
PR3000RTXL2UA SE450G1
Model Number
PR3000RTXL2UA SE450G1
Additional Model Information
PR2200RT2U JP,PR2200RT2U JP,; PR2200RT2U,PR2200RT2U,; PR2200RT2UC,PR2200RT2UC,; PR2200RT2UCN,PR2200RT2UCN,; PR2200RTXL2U JP,PR2200RTXL2U JP,; PR2200RTXL2U,PR2200RTXL2U,; PR2200RTXL2UA JP,PR2200RTXL2UA JP,; PR2200RTXL2UA,PR2200RTXL2UA,; PR2200RTXL2UAC,PR2200RTXL2UAC,; PR2200RTXL2UACN,PR2200RTXL2UACN,; PR2200RTXL2UC,PR2200RTXL2UC,; PR2200RTXL2UCN,PR2200RTXL2UCN,; PR3000RT2U JP,PR3000RT2U JP,; PR3000RT2U,PR3000RT2U,; PR3000RT2UC,PR3000RT2UC,; PR3000RT2UCN,PR3000RT2UCN,; PR3000RTXL2U JP,PR3000RTXL2U JP,; PR3000RTXL2U,PR3000RTXL2U,; PR3000RTXL2UA JP,PR3000RTXL2UA JP,; PR3000RTXL2UAC,PR3000RTXL2UAC,; PR3000RTXL2UACN,PR3000RTXL2UACN,; PR3000RTXL2UC,PR3000RTXL2UC,; PR3000RTXL2UCN,PR3000RTXL2UCN,; PRL3000RT2UC,PRL3000RT2UC,; PRL3000RT2UCN,PRL3000RT2UCN, N/A
Date Available On Market
August 1, 2018 May 15, 2018
Date Certified
January 17, 2023 April 11, 2018
Markets
United States, Taiwan, Japan, Canada United States
CB Model Identifier
ES_1095904_PR3000RTXL2UA_07292018101208_9128733 ES_1095904_SE450G1_05202018125226_0746423
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
PR2200RTXL2UA SE450G1
Active Output Power Rating Minimum Configuration (W)
2,200 260
Apparent Output Power Rating Minimum Configuration (VA)
2,200 450
Maximum Configuration Tested Model Number
PR3000RTXL2UA N/A
Active Output Power Rating Maximum Configuration (W)
3,000 N/A
Topology (ac)
Line Interactive Passive Standby
Topology and Product Type Combined
ac Line Interactive (VI) Alternating Current (ac) - Offline (VFD)
Application
Consumer Consumer
Rated Input Voltage (V rms)
100-120 120-120
Rated Input Frequency (Hz)
50-60 50-60
Rated Output Voltage (V)
100-120 120-120
Rated Output Frequency (Hz)
50-60 50-60
Rack Mountable
Yes No
Rack Mount Height (U)
2 N/A
Height (mm)
87 210
Width (mm)
433 115
Depth (mm)
630 81
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage Independent Voltage and Frequency Dependent
Modular UPS
No No
Number of Normal Modes
Single-normal-mode Single-normal-mode
Default Normal Mode (ac)
Voltage Independent Voltage and Frequency Dependent
Test Input Voltage (V rms)
120 120
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
120 120
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
4 2.92
Efficiency at 25% Load Min Config Lowest Dependency (ac)
98 95.5
Efficiency at 50% Load Min Config Lowest Dependency (ac)
98 97.9
Efficiency at 75% Load Min Config Lowest Dependency (ac)
98 98.4
Efficiency at 100% Load Min Config Lowest Dependency (ac)
98 98.5
Weighted Efficiency Calc Min Config Lowest Dependency
98 97.8
Total Input Power in W at 0% Load Max Config Lowest Dependency (ac)
5 N/A
Efficiency at 25% Load Max Config Lowest Dependency (ac)
99 N/A
Efficiency at 50% Load Max Config Lowest Dependency (ac)
99 N/A
Efficiency at 75% Load Max Config Lowest Dependency (ac)
99 N/A
Efficiency at 100% Load Max Config Lowest Dependency (ac)
98 N/A
Weighted Efficiency Calc Max Config Lowest Dependency
99 N/A
Efficiency (%)
98 97.8
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Integral Integral
Energy Storage System Removable to Another Room
No N/A
Energy Storage System Runtime at 100% Load (min.)
4 2
Energy Storage System Runtime at 50% Load (min.)
11 6
Energy Storage System Warranty (yrs)
3 3
Energy Storage System Information URL
N/A N/A
Network Connections Available
Serial Port,Ethernet,USB Port None
Communication Protocols
HTTP,HTTPS,Other,SNMP (v1, 2 or 3) None
Communication Protocol Other
TCP/IP, UDP N/A
Manufacturer Take Back Program
Yes No
Model Web Page URL
N/A N/A
Test Method Guidelines
N/A N/A
Date Qualified
January 17, 2023 April 11, 2018