Compare CyberPower – PR3000RTXL2UHVA vs CyberPower – OL1500RTXL2UNTAA Specifications

PR3000RTXL2UHVA OL1500RTXL2UNTAA
ENERGY STAR Partner
Cyber Power Systems, Inc. Cyber Power Systems, Inc.
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
CyberPower CyberPower
Model Name
PR3000RTXL2UHVA OL1500RTXL2UNTAA
Model Number
PR3000RTXL2UHVA OL1500RTXL2UNTAA
Additional Model Information
ELITE PRO 2200ERTXL2UA,ELITE PRO 2200ERTXL2UA,; ELITE PRO 3000ERT2U,ELITE PRO 3000ERT2U,; ELITE PRO 3000ERTXL2U,ELITE PRO 3000ERTXL2U,; ELITE PRO 3000ERTXL2UA,ELITE PRO 3000ERTXL2UA,; PR2200ERTXL2UA JP,PR2200ERTXL2UA JP,; PR2200ERTXL2UA,PR2200ERTXL2UA,; PR2200RTXL2UHVA JP,PR2200RTXL2UHVA JP,; PR2200RTXL2UHVA,PR2200RTXL2UHVA,; PR3000ERT2U JP,PR3000ERT2U JP,; PR3000ERT2U,PR3000ERT2U,; PR3000ERTXL2U JP,PR3000ERTXL2U JP,; PR3000ERTXL2U,PR3000ERTXL2U,; PR3000ERTXL2UA JP,PR3000ERTXL2UA JP,; PR3000ERTXL2UA,PR3000ERTXL2UA,; PR3000RTXL2UHVA JP,PR3000RTXL2UHVA JP,; PX2200ERTXL2U,PX2200ERTXL2U,; PX3000ERTXL2U,PX3000ERTXL2U, N/A
Date Available On Market
August 1, 2018 July 1, 2013
Date Certified
January 17, 2023 September 19, 2018
Markets
United States, Taiwan, Japan, Canada United States
CB Model Identifier
ES_1095904_PR3000RTXL2UHVA_07132018092130_3690657 ES_1095904_OL1500RTXL2UNTAA_09192018094841_0521558
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
PR3000RTXL2UHVA OL1500RTXL2U
Active Output Power Rating Minimum Configuration (W)
3,000 1350
Apparent Output Power Rating Minimum Configuration (VA)
3,000 1500
Topology (ac)
Line Interactive Double Conversion
Topology and Product Type Combined
ac Line Interactive (VI) ac - Double Conversion (VFI)
Application
Consumer Commercial,Consumer
Rated Input Voltage (V rms)
200-240 100-125
Rated Input Frequency (Hz)
50-60 50-60
Rated Output Voltage (V)
200-240 100-125
Rated Output Frequency (Hz)
50-60 50-60
Rack Mountable
Yes Yes
Rack Mount Height (U)
2 2
Height (mm)
87 88
Width (mm)
433 433
Depth (mm)
630 430
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage Independent Voltage and Frequency Dependent,Voltage and Frequency Independent
Modular UPS
No No
Number of Normal Modes
Single-normal-mode Multiple-normal-mode
Default Normal Mode (ac)
Voltage Independent Voltage and Frequency Independent
Test Input Voltage (V rms)
230 120
Test Input Frequency (Hz)
6,050 60
Test Output Voltage (V)
230 120
Test Output Frequency (Hz)
50 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
6 23.59
Efficiency at 25% Load Min Config Lowest Dependency (ac)
99 88.7
Efficiency at 50% Load Min Config Lowest Dependency (ac)
99 91.1
Efficiency at 75% Load Min Config Lowest Dependency (ac)
99 91
Efficiency at 100% Load Min Config Lowest Dependency (ac)
99 90.6
Weighted Efficiency Calc Min Config Lowest Dependency
99 90.9
Efficiency (%)
99 90.9
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Integral Integral
Energy Storage System Removable to Another Room
No No
Energy Storage System Runtime at 100% Load (min.)
4 4
Energy Storage System Runtime at 50% Load (min.)
11 11
Energy Storage System Warranty (yrs)
3 3
Energy Storage System Information URL
N/A http://www.cyberpowersystems.com/
Network Connections Available
Serial Port,Ethernet,USB Port Serial Port,USB Port,Ethernet
Communication Protocols
HTTP,HTTPS,Other,SNMP (v1, 2 or 3) HTTPS,HTTP,SNMP (v1, 2 or 3)
Communication Protocol Other
TCP/IP, UDP N/A
Manufacturer Take Back Program
Yes Yes
Model Web Page URL
N/A http://www.cyberpowersystems.com
Test Method Guidelines
N/A http://www.cyberpowersystems.com/
Date Qualified
January 17, 2023 September 19, 2018

Compare CyberPower - PR3000RTXL2UHVA With Other 105 Models

Scroll to Top