ENERGY STAR Partner |
Cyber Power Systems, Inc. |
Cyber Power Systems, Inc. |
Product Category |
Uninterruptible Power Supplies |
Uninterruptible Power Supplies |
Type |
Ac-output UPS |
Ac-output UPS |
Brand Name |
CyberPower |
CyberPower |
Model Name |
SX650U |
OL6KRTHDL (with cord connected) |
Model Number |
SX650U |
OL6KRTHDL |
Date Available On Market |
May 15, 2018 |
October 31, 2023 |
Date Certified |
April 11, 2018 |
April 2, 2019 |
Markets |
United States |
United States |
CB Model Identifier |
ES_1095904_SX650U_05202018130014_1214363 |
ES_1095904_OL6KRTHDL_091420231055188_2617984 |
Meets ENERGY STAR Most Efficient 2024 Criteria |
No |
No |
Power Conversion Mechanism |
Static |
Static |
Minimum Configuration Tested Model Number |
SX650U |
OL5KRTHD (with cord connected) |
Active Output Power Rating Minimum Configuration (W) |
360 |
5000 |
Apparent Output Power Rating Minimum Configuration (VA) |
650 |
5000 |
Topology (ac) |
Passive Standby |
Double Conversion |
Topology and Product Type Combined |
Alternating Current (ac) - Offline (VFD) |
ac - Double Conversion (VFI) |
Application |
Consumer |
Data Center,Consumer,Commercial |
Rated Input Voltage (V rms) |
120-120 |
200-240 |
Rated Input Frequency (Hz) |
50-60 |
50-60 |
Rated Output Voltage (V) |
120-120 |
200-240 |
Rated Output Frequency (Hz) |
50-60 |
50-60 |
Rack Mountable |
No |
Yes |
Height (mm) |
250 |
130 |
Width (mm) |
147 |
433 |
Depth (mm) |
82 |
720 |
Normal Mode(s) Input Dependency Characteristic (ac) |
Voltage and Frequency Dependent |
Voltage and Frequency Independent,Voltage and Frequency Dependent |
Modular UPS |
No |
No |
Number of Normal Modes |
Single-normal-mode |
Multiple-normal-mode |
Default Normal Mode (ac) |
Voltage and Frequency Dependent |
Voltage and Frequency Independent |
Test Input Voltage (V rms) |
120 |
240 |
Test Input Frequency (Hz) |
60 |
60 |
Test Output Voltage (V) |
120 |
240 |
Test Output Frequency (Hz) |
60 |
60 |
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac) |
3 |
78.89 |
Efficiency at 25% Load Min Config Lowest Dependency (ac) |
97 |
91 |
Efficiency at 50% Load Min Config Lowest Dependency (ac) |
98 |
93.4 |
Efficiency at 75% Load Min Config Lowest Dependency (ac) |
99 |
93.7 |
Efficiency at 100% Load Min Config Lowest Dependency (ac) |
99 |
93.6 |
Weighted Efficiency Calc Min Config Lowest Dependency |
98 |
93.6 |
Efficiency (%) |
98 |
93.7 |
Modular UPS Module Tested Model Number |
N/A |
N/A |
Energy Storage Mechanism |
Battery |
Battery |
Energy Storage System Technology |
Valve Regulated Lead-acid Battery |
Valve Regulated Lead-acid Battery |
Energy Storage System Configuration |
Integral |
Integral |
Energy Storage System Removable to Another Room |
N/A |
No |
Energy Storage System Runtime at 100% Load (min.) |
2 |
2 |
Energy Storage System Runtime at 50% Load (min.) |
9 |
5 |
Energy Storage System Warranty (yrs) |
3 |
3 |
Energy Storage System Information URL |
N/A |
http://www.cyberpowersystems.com/ |
Network Connections Available |
USB Port |
Serial Port,Ethernet,USB Port |
Communication Protocols |
None |
HTTP,HTTPS,SNMP (v1, 2 or 3) |
Manufacturer Take Back Program |
No |
Yes |
Model Web Page URL |
N/A |
http://www.cyberpowersystems.com/ |
Test Method Guidelines |
N/A |
http://www.cyberpowersystems.com/ |
Date Qualified |
April 11, 2018 |
April 2, 2019 |