ENERGY STAR Partner |
Cyber Power Systems, Inc. |
Cyber Power Systems, Inc. |
Product Category |
Uninterruptible Power Supplies |
Uninterruptible Power Supplies |
Type |
Ac-output UPS |
Ac-output UPS |
Brand Name |
CyberPower |
CyberPower |
Model Name |
SX950U |
OL3000RTXL2UN |
Model Number |
SX950U |
OL3000RTXL2UN |
Date Available On Market |
May 15, 2018 |
July 1, 2013 |
Date Certified |
April 11, 2018 |
September 19, 2018 |
Markets |
United States |
United States |
CB Model Identifier |
ES_1095904_SX950U_05202018130453_1493920 |
ES_1095904_OL3000RTXL2UN_09192018083824_6304201 |
Meets ENERGY STAR Most Efficient 2024 Criteria |
No |
No |
Power Conversion Mechanism |
Static |
Static |
Minimum Configuration Tested Model Number |
SX950U |
OL3000RTXL2U |
Active Output Power Rating Minimum Configuration (W) |
510 |
2700 |
Apparent Output Power Rating Minimum Configuration (VA) |
950 |
3000 |
Topology (ac) |
Passive Standby |
Double Conversion |
Topology and Product Type Combined |
Alternating Current (ac) - Offline (VFD) |
ac - Double Conversion (VFI) |
Application |
Consumer |
Commercial,Consumer |
Rated Input Voltage (V rms) |
120-120 |
100-125 |
Rated Input Frequency (Hz) |
50-60 |
50-60 |
Rated Output Voltage (V) |
120-120 |
100-125 |
Rated Output Frequency (Hz) |
50-60 |
50-60 |
Rack Mountable |
No |
Yes |
Height (mm) |
310 |
88 |
Width (mm) |
178 |
433 |
Depth (mm) |
80 |
600 |
Normal Mode(s) Input Dependency Characteristic (ac) |
Voltage and Frequency Dependent |
Voltage and Frequency Dependent,Voltage and Frequency Independent |
Modular UPS |
No |
No |
Number of Normal Modes |
Single-normal-mode |
Multiple-normal-mode |
Default Normal Mode (ac) |
Voltage and Frequency Dependent |
Voltage and Frequency Independent |
Test Input Voltage (V rms) |
120 |
120 |
Test Input Frequency (Hz) |
60 |
60 |
Test Output Voltage (V) |
120 |
120 |
Test Output Frequency (Hz) |
60 |
60 |
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac) |
3 |
46.93 |
Efficiency at 25% Load Min Config Lowest Dependency (ac) |
97 |
89.8 |
Efficiency at 50% Load Min Config Lowest Dependency (ac) |
99 |
91.7 |
Efficiency at 75% Load Min Config Lowest Dependency (ac) |
99 |
91.6 |
Efficiency at 100% Load Min Config Lowest Dependency (ac) |
99 |
91.2 |
Weighted Efficiency Calc Min Config Lowest Dependency |
98 |
91.5 |
Efficiency (%) |
98 |
91.5 |
Modular UPS Module Tested Model Number |
N/A |
N/A |
Energy Storage Mechanism |
Battery |
Battery |
Energy Storage System Technology |
Valve Regulated Lead-acid Battery |
Valve Regulated Lead-acid Battery |
Energy Storage System Configuration |
Integral |
Integral |
Energy Storage System Removable to Another Room |
N/A |
No |
Energy Storage System Runtime at 100% Load (min.) |
2 |
4 |
Energy Storage System Runtime at 50% Load (min.) |
8 |
11 |
Energy Storage System Warranty (yrs) |
3 |
3 |
Energy Storage System Information URL |
N/A |
http://www.cyberpowersystems.com/ |
Network Connections Available |
USB Port |
Serial Port,USB Port,Ethernet |
Communication Protocols |
None |
HTTPS,HTTP,SNMP (v1, 2 or 3) |
Manufacturer Take Back Program |
No |
Yes |
Model Web Page URL |
N/A |
http://www.cyberpowersystems.com |
Test Method Guidelines |
N/A |
http://www.cyberpowersystems.com/ |
Date Qualified |
April 11, 2018 |
September 19, 2018 |