Compare Delta – RT-3K vs Delta – RT-20K3P Specifications

RT-3K RT-20K3P
ENERGY STAR Partner
Delta Electronics, Inc. Tainan Branch Delta Electronics, Inc. Tainan Branch
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
Delta Delta
Model Name
RT-3K RT-20K3P
Model Number
RT-3K RT-20K3P
Date Available On Market
November 1, 2018 July 14, 2019
Date Certified
September 19, 2018 June 27, 2019
Markets
United States, Taiwan, Canada United States, Taiwan, Canada
CB Model Identifier
ES_1140198_RT-3K_09192018065205_9925142 ES_1140198_RT-20K3P_06282019060609_1969909
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
RT-3K RT-20K3P
Active Output Power Rating Minimum Configuration (W)
2,700 20000
Apparent Output Power Rating Minimum Configuration (VA)
3,000 20000
Topology (ac)
Double Conversion Double Conversion
Topology and Product Type Combined
ac - Double Conversion (VFI) ac - Double Conversion (VFI)
Application
Consumer Data Center,Consumer,Commercial
Rated Input Voltage (V rms)
100-120 220-240
Rated Input Frequency (Hz)
50-60 50-60
Rated Output Voltage (V)
100-120 220-240
Rated Output Frequency (Hz)
50-60 50-60
Rack Mountable
Yes Yes
Height (mm)
88 88
Width (mm)
440 440
Depth (mm)
565 730
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage and Frequency Independent Voltage and Frequency Independent
Modular UPS
No No
Number of Normal Modes
Single-normal-mode Single-normal-mode
Default Normal Mode (ac)
Voltage and Frequency Independent Voltage and Frequency Independent
Test Input Voltage (V rms)
120 240
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
120 240
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
54 189.3
Efficiency at 25% Load Min Config Lowest Dependency (ac)
87 95
Efficiency at 50% Load Min Config Lowest Dependency (ac)
91 96
Efficiency at 75% Load Min Config Lowest Dependency (ac)
92 96
Efficiency at 100% Load Min Config Lowest Dependency (ac)
92 95.9
Weighted Efficiency Calc Min Config Lowest Dependency
92 95.7
Efficiency (%)
92 95.7
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Integral Integral
Energy Storage System Removable to Another Room
N/A N/A
Energy Storage System Runtime at 100% Load (min.)
3 3
Energy Storage System Runtime at 50% Load (min.)
12 10
Energy Storage System Warranty (yrs)
3 3
Energy Storage System Information URL
N/A N/A
Network Connections Available
Serial Port,Ethernet,USB Port Serial Port,Ethernet,USB Port
Communication Protocols
Other Other
Communication Protocol Other
USB HID Power Devices USB HID Power Devices
Manufacturer Take Back Program
No No
Model Web Page URL
N/A N/A
Test Method Guidelines
N/A N/A
Date Qualified
September 19, 2018 June 27, 2019

Compare Delta - RT-3K With Other 22 Models