Product Program Category |
Uninterruptible Power Supplies |
N/A |
Type |
Ac-output UPS |
Ac-output UPS |
Brand Name |
Eaton Brand UPS |
Eaton Brand UPS |
Model Name |
9PX1000IRT2U-L |
5PX2200IRT2UG2 |
Model Number |
9PX1000IRT2U-L |
5PX2200IRT2UG2 |
UPC |
743,172,105,486 |
N/A |
CB Model Identifier |
ES_29597_9PX1000IRT2U-L_07132021114439_2123579 |
ES_29597_5PX2200IRT2UG2_06182021155249_2749755 |
Meets ENERGY STAR Most Efficient 2024 Criteria |
No |
No |
ENERGY STAR Partner |
Eaton Corporation |
Eaton Corporation |
Product Category |
Uninterruptible Power Supplies |
Uninterruptible Power Supplies |
Additional Model Information |
9PX1000IRTANZ-L,9PX1000IRTANZ-L,a; 9PX1000IRTIND-L,9PX1000IRTIND-L,b |
5PX2200HRTG2,5PX2200HRTG2,d; 5PX2200IRT2UAUG2,5PX2200IRT2UAUG2,c; 5PX2200IRT2UTHG2,5PX2200IRT2UTHG2,b; 5PX2200IRTNG2,5PX2200IRTNG2,a |
Date Available On Market |
January 9, 2021 |
January 9, 2021 |
Date Certified |
July 12, 2021 |
June 17, 2021 |
Markets |
United States, Switzerland, Taiwan, Japan, Canada |
United States, Switzerland, Taiwan, Japan, Canada |
Power Conversion Mechanism |
Static |
Static |
Minimum Configuration Tested Model Number |
9PX1000IRT2U-L |
5PX2200IRT2UG2 |
Active Output Power Rating Minimum Configuration (W) |
1,000 |
2200 |
Apparent Output Power Rating Minimum Configuration (VA) |
1,000 |
2200 |
Topology (ac) |
Double Conversion |
Line Interactive |
Topology and Product Type Combined |
ac - Double Conversion (VFI) |
ac Line Interactive (VI) |
Application |
Data Center,Consumer,Commercial |
Data Center,Consumer,Commercial |
Rated Input Voltage (V rms) |
200-240 |
603-240 |
Rated Input Frequency (Hz) |
50-60 |
50-60 |
Rated Output Voltage (V) |
200-240 |
200-240 |
Rated Output Frequency (Hz) |
50-60 |
50-60 |
Rack Mountable |
Yes |
Yes |
Rack Mount Height (U) |
2 |
2 |
Height (mm) |
86 |
86 |
Width (mm) |
440 |
438 |
Depth (mm) |
450 |
603 |
Normal Mode(s) Input Dependency Characteristic (ac) |
Voltage and Frequency Independent |
Voltage Independent |
Modular UPS |
No |
No |
Number of Normal Modes |
Single-normal-mode |
Single-normal-mode |
Default Normal Mode (ac) |
Voltage and Frequency Independent |
Voltage Independent |
Test Input Voltage (V rms) |
230 |
230 |
Test Input Frequency (Hz) |
60 |
50 |
Test Output Voltage (V) |
230 |
230 |
Test Output Frequency (Hz) |
60 |
50 |
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac) |
35 |
12.85 |
Efficiency at 25% Load Min Config Lowest Dependency (ac) |
85 |
N/A |
Efficiency at 50% Load Min Config Lowest Dependency (ac) |
90 |
98.2 |
Efficiency at 75% Load Min Config Lowest Dependency (ac) |
92 |
98.4 |
Efficiency at 100% Load Min Config Lowest Dependency (ac) |
93 |
98.3 |
Weighted Efficiency Calc Min Config Lowest Dependency |
92 |
98.3 |
Minimum Configuration Input Power Factor Lowest-Input Dependency |
1 |
1 |
Efficiency (%) |
92 |
98.3 |
Modular UPS Module Tested Model Number |
N/A |
N/A |
Energy Storage Mechanism |
Battery |
Battery |
Energy Storage System Technology |
Lithium-ion Battery |
Valve Regulated Lead-acid Battery |
Energy Storage System Configuration |
Integral |
Separate Enclosure |
Energy Storage System Removable to Another Room |
Yes |
Yes |
Energy Storage System Runtime at 100% Load (min.) |
4 |
3 |
Energy Storage System Runtime at 50% Load (min.) |
9 |
10 |
Energy Storage System Warranty (yrs) |
2 |
2 |
Energy Storage System Information URL |
https://www.eaton.com/us/en-us.html |
www.eaton.com/us/en-us.html |
Battery Recycling URL |
www.eaton.com/recycling |
www.eaton.com/recycling |
Network Connections Available |
Other |
Other |
Communication Protocols |
Other |
Other |
Communication Protocol Other |
Eaton Shut |
Eaton Shut |
Manufacturer Take Back Program |
No |
No |
Manufacturer Take Back Program URL |
www.eaton.com/recycling |
www.eaton.com/recycling |
Model Web Page URL |
www.eaton.com |
www.eaton.com |
Test Method Guidelines |
N/A |
N/A |
Date Qualified |
July 12, 2021 |
June 17, 2021 |