Compare Liebert – EXS 0040kTH16FN01000 vs Liebert – 53[S|P]10[A|B|E|F][C|Y][0-4][0|A|C|D|Q][0-8|A-E][0-9|A-H|J|K|L|W|X|Y][0][0-9|A-Z][0-9|A-Z][0-9|A-Z] Specifications

EXS 0040kTH16FN01000 53[S|P]10[A|B|E|F][C|Y][0-4][0|A|C|D|Q][0-8|A-E][0-9|A-H|J|K|L|W|X|Y][0][0-9|A-Z][0-9|A-Z][0-9|A-Z]
ENERGY STAR Partner
Vertiv Corporation Vertiv Corporation
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
Liebert Liebert
Model Name
Liebert EXS Liebert EXS F1
Model Number
EXS 0040kTH16FN01000 53[S|P]10[A|B|E|F][C|Y][0-4][0|A|C|D|Q][0-8|A-E][0-9|A-H|J|K|L|W|X|Y][0][0-9|A-Z][0-9|A-Z][0-9|A-Z]
Additional Model Information
Liebert EXS F2 series,EXS 0030kTH16FN01000, N/A
Date Available On Market
May 1, 2018 January 31, 2018
Date Certified
August 1, 2018 January 23, 2019
Markets
United States, Switzerland, Taiwan, Japan, Canada United States, Taiwan, Japan, Canada
CB Model Identifier
ES_1097807_EXS 0040kTH16FN01000_08022018105614_7374729 ES_1097807_53[S|P]10[A|B|E|F][C|Y][0-4][0|A|C|D|Q]_03272019084034_6034522
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
EXS 0040kTH16FN01000 53S010AC10000000000000000
Active Output Power Rating Minimum Configuration (W)
40,000 10000
Apparent Output Power Rating Minimum Configuration (VA)
40,000 10000
Topology (ac)
Multi-Mode Double Conversion Multi-Mode Double Conversion
Topology and Product Type Combined
ac - Other ac - Other
Application
Commercial,Consumer,Data Center Commercial,Consumer,Data Center
Rated Input Voltage (V rms)
380-415 208-220
Rated Input Frequency (Hz)
50-60 50-60
Rated Output Voltage (V)
380-415 208-220
Rated Output Frequency (Hz)
50-60 50-60
Rack Mountable
No No
Height (mm)
1,600 1300
Width (mm)
440 334
Depth (mm)
749 650
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage and Frequency Dependent,Voltage and Frequency Independent Voltage and Frequency Dependent,Voltage and Frequency Independent
Modular UPS
No No
Number of Normal Modes
Multiple-normal-mode Multiple-normal-mode
Default Normal Mode (ac)
Voltage and Frequency Independent Voltage and Frequency Dependent
Test Input Voltage (V rms)
415 208
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
415 208
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
263 79.27
Efficiency at 25% Load Min Config Lowest Dependency (ac)
95 92.4
Efficiency at 50% Load Min Config Lowest Dependency (ac)
96 93.4
Efficiency at 75% Load Min Config Lowest Dependency (ac)
96 93.1
Efficiency at 100% Load Min Config Lowest Dependency (ac)
95 92.5
Weighted Efficiency Calc Min Config Lowest Dependency
96 93
Minimum Configuration Input Power Factor Lowest-Input Dependency
1 0.99
Efficiency (%)
96 94.5
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Separate Enclosure Integral
Energy Storage System Removable to Another Room
No Yes
Energy Storage System Runtime at 100% Load (min.)
10 20
Energy Storage System Runtime at 50% Load (min.)
20 53
Energy Storage System Warranty (yrs)
1 1
Energy Storage System Information URL
http://www.enersys.com/ http://www.eastpennunigy.com/ N/A
Network Connections Available
None Serial Port,Other,USB Port,Ethernet
Communication Protocols
Other Modbus TCP,HTTPS,Other,HTTP,SNMP (v1, 2 or 3),Modbus RTU
Manufacturer Take Back Program
No No
Model Web Page URL
https://www.vertivco.com/en-us/products-catalog/critical-power/uninterruptible-power-supplies-ups/ www.vertivco.com
Test Method Guidelines
N/A N/A
Date Qualified
August 1, 2018 January 23, 2019