Compare Liebert – GXT5-1000LVRT2UXL vs Liebert – 53[S|P]10[A|B|E|F][C|Y][0-4][0|A|C|D|Q][0-8|A-E][0-9|A-H|J|K|L|W|X|Y][0][0-9|A-Z][0-9|A-Z][0-9|A-Z] Specifications

GXT5-1000LVRT2UXL 53[S|P]10[A|B|E|F][C|Y][0-4][0|A|C|D|Q][0-8|A-E][0-9|A-H|J|K|L|W|X|Y][0][0-9|A-Z][0-9|A-Z][0-9|A-Z]
ENERGY STAR Partner
Vertiv Corporation Vertiv Corporation
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
Liebert Liebert
Model Name
GXT5-1000LVRT2UXL Liebert EXS F1
Model Number
GXT5-1000LVRT2UXL 53[S|P]10[A|B|E|F][C|Y][0-4][0|A|C|D|Q][0-8|A-E][0-9|A-H|J|K|L|W|X|Y][0][0-9|A-Z][0-9|A-Z][0-9|A-Z]
Additional Model Information
GXT5-750LVRT2UXL,GXT5-750LVRT2UXL, N/A
Date Available On Market
December 1, 2018 January 31, 2018
Date Certified
December 6, 2018 January 23, 2019
Markets
United States, Taiwan, Japan, Canada United States, Taiwan, Japan, Canada
CB Model Identifier
ES_1097807_GXT5-1000LVRT2UXL_12072018022711_9631677 ES_1097807_53[S|P]10[A|B|E|F][C|Y][0-4][0|A|C|D|Q]_03272019084034_6034522
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
GXT5-1000LVRT2UXL 53S010AC10000000000000000
Active Output Power Rating Minimum Configuration (W)
1,000 10000
Apparent Output Power Rating Minimum Configuration (VA)
1,000 10000
Topology (ac)
Multi-Mode Double Conversion Multi-Mode Double Conversion
Topology and Product Type Combined
ac - Other ac - Other
Application
Commercial,Consumer,Data Center Commercial,Consumer,Data Center
Rated Input Voltage (V rms)
110-125 208-220
Rated Input Frequency (Hz)
50-60 50-60
Rated Output Voltage (V)
110-125 208-220
Rated Output Frequency (Hz)
50-60 50-60
Rack Mountable
Yes No
Height (mm)
85 1300
Width (mm)
430 334
Depth (mm)
400 650
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage and Frequency Dependent,Voltage and Frequency Independent Voltage and Frequency Dependent,Voltage and Frequency Independent
Modular UPS
No No
Number of Normal Modes
Multiple-normal-mode Multiple-normal-mode
Default Normal Mode (ac)
Voltage and Frequency Independent Voltage and Frequency Dependent
Test Input Voltage (V rms)
120 208
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
120 208
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
26 79.27
Efficiency at 25% Load Min Config Lowest Dependency (ac)
87 92.4
Efficiency at 50% Load Min Config Lowest Dependency (ac)
91 93.4
Efficiency at 75% Load Min Config Lowest Dependency (ac)
91 93.1
Efficiency at 100% Load Min Config Lowest Dependency (ac)
90 92.5
Weighted Efficiency Calc Min Config Lowest Dependency
91 93
Minimum Configuration Input Power Factor Lowest-Input Dependency
1 0.99
Efficiency (%)
91 94.5
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Separate Enclosure Integral
Energy Storage System Removable to Another Room
No Yes
Energy Storage System Runtime at 100% Load (min.)
6 20
Energy Storage System Runtime at 50% Load (min.)
15 53
Energy Storage System Warranty (yrs)
2 1
Energy Storage System Information URL
http://www.enersys.com/ http://www.eastpennunigy.com/ N/A
Network Connections Available
USB Port,Ethernet Serial Port,Other,USB Port,Ethernet
Communication Protocols
Other Modbus TCP,HTTPS,Other,HTTP,SNMP (v1, 2 or 3),Modbus RTU
Manufacturer Take Back Program
No No
Model Web Page URL
https://www.vertivco.com/en-us/products-catalog/critical-power/uninterruptible-power-supplies-ups/ www.vertivco.com
Test Method Guidelines
N/A N/A
Date Qualified
December 6, 2018 January 23, 2019

Compare Liebert - GXT5-1000LVRT2UXL With Other 72 Models