Compare Liebert – GXT5-1000LVRT2UXL vs Liebert – GXT5LI-10KMVRT4XN-P Specifications

GXT5-1000LVRT2UXL GXT5LI-10KMVRT4XN-P
ENERGY STAR Partner
Vertiv Corporation Vertiv Corporation
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
Liebert Liebert
Model Name
GXT5-1000LVRT2UXL GXT5LI-10KMVRT4XN-P
Model Number
GXT5-1000LVRT2UXL GXT5LI-10KMVRT4XN-P
Additional Model Information
GXT5-750LVRT2UXL,GXT5-750LVRT2UXL, GXT5LI-10KRT4XN-P,GXT5LI-10KRT4XN-P,
Date Available On Market
December 1, 2018 May 1, 2023
Date Certified
December 6, 2018 June 29, 2023
Markets
United States, Taiwan, Japan, Canada United States, Taiwan, Japan, Canada
CB Model Identifier
ES_1097807_GXT5-1000LVRT2UXL_12072018022711_9631677 ES_1097807_GXT5LI-10KMVRT4XN-P_06282023172689_5921689
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
GXT5-1000LVRT2UXL 1
Active Output Power Rating Minimum Configuration (W)
1,000 10000
Apparent Output Power Rating Minimum Configuration (VA)
1,000 10000
Topology (ac)
Multi-Mode Double Conversion Multi-Mode Double Conversion
Topology and Product Type Combined
ac - Other ac - Other
Application
Commercial,Consumer,Data Center Data Center,Commercial
Rated Input Voltage (V rms)
110-125 120-240
Rated Input Frequency (Hz)
50-60 50-60
Rated Output Voltage (V)
110-125 120-240
Rated Output Frequency (Hz)
50-60 50-60
Rack Mountable
Yes Yes
Height (mm)
85 3
Width (mm)
430 17
Depth (mm)
400 37
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage and Frequency Dependent,Voltage and Frequency Independent Voltage and Frequency Independent
Modular UPS
No No
Number of Normal Modes
Multiple-normal-mode Single-normal-mode
Default Normal Mode (ac)
Voltage and Frequency Independent Voltage and Frequency Independent
Test Input Voltage (V rms)
120 120
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
120 120
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
26 53.78
Efficiency at 25% Load Min Config Lowest Dependency (ac)
87 94.2
Efficiency at 50% Load Min Config Lowest Dependency (ac)
91 94.2
Efficiency at 75% Load Min Config Lowest Dependency (ac)
91 93.6
Efficiency at 100% Load Min Config Lowest Dependency (ac)
90 92.7
Weighted Efficiency Calc Min Config Lowest Dependency
91 93.5
Minimum Configuration Input Power Factor Lowest-Input Dependency
1 N/A
Efficiency (%)
91 93.5
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Lithium-ion Battery
Energy Storage System Configuration
Separate Enclosure Integral
Energy Storage System Removable to Another Room
No N/A
Energy Storage System Runtime at 100% Load (min.)
6 10
Energy Storage System Runtime at 50% Load (min.)
15 21
Energy Storage System Warranty (yrs)
2 5
Energy Storage System Information URL
http://www.enersys.com/ http://www.eastpennunigy.com/ www.vertiv.com/en-us/products-catalog/critical-power/uninterruptible-power-supplies-ups/gxt5li-10kmvrt4uxln/#/downloads
Network Connections Available
USB Port,Ethernet Serial Port,Ethernet,USB Port
Communication Protocols
Other HTTPS,SNMP (v1, 2 or 3)
Manufacturer Take Back Program
No No
Model Web Page URL
https://www.vertivco.com/en-us/products-catalog/critical-power/uninterruptible-power-supplies-ups/ www.vertiv.com/en-us/products-catalog/critical-power/uninterruptible-power-supplies-ups/gxt5li-10kmvrt4uxln/#/downloads
Test Method Guidelines
N/A www.vertiv.com/en-us/products-catalog/critical-power/uninterruptible-power-supplies-ups/gxt5li-10kmvrt4uxln/#/downloads
Date Qualified
December 6, 2018 June 29, 2023

Compare Liebert - GXT5-1000LVRT2UXL With Other 72 Models

Scroll to Top