Compare Middle Atlantic – UPX-2000R-8 vs Middle Atlantic – UPX-OL1500R-2 Specifications

UPX-2000R-8 UPX-OL1500R-2
ENERGY STAR Partner
Legrand AV Inc. Legrand AV Inc.
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
Middle Atlantic Middle Atlantic
Model Name
UPX-2000R-8 UPX-OL1500R-2
Model Number
UPX-2000R-8 UPX-OL1500R-2
Additional Model Information
UPX-2000R-2, UPX-RLNK-2000R-2, UPX-RLNK-2000R-8,UPX-2000R-2, UPX-RLNK-2000R-2, UPX-RLNK-2000R-8, UPX-OL1500R-8,UPX-OL1500R-8,; UPX-RLNK-1500R-2,UPX-RLNK-1500R-2,; UPX-RLNK-1500R-8,UPX-RLNK-1500R-8,
Date Available On Market
June 1, 2022 December 15, 2023
Date Certified
April 29, 2022 November 14, 2023
Markets
United States United States, Canada
CB Model Identifier
ES_1147429_UPX-2000R-2_04292022153948_3182878 ES_1147429_UPX-OL1500R-2_11152023144347_5966140
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
N/A N/A
Active Output Power Rating Minimum Configuration (W)
1,800 1350
Apparent Output Power Rating Minimum Configuration (VA)
2,000 1500
Maximum Configuration Tested Model Number
N/A N/A
Topology (ac)
Line Interactive Other
Topology and Product Type Combined
ac Line Interactive (VI) ac - Other
Application
Commercial Commercial
Rated Input Voltage (V rms)
110-127 110-127
Rated Input Frequency (Hz)
50-60 50-60
Rated Output Voltage (V)
110-127 110-127
Rated Output Frequency (Hz)
50-60 50-60
Rack Mountable
Yes Yes
Rack Mount Height (U)
2 N/A
Height (mm)
87 87
Width (mm)
600 450
Depth (mm)
440 440
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage Independent Voltage and Frequency Independent
Modular UPS
No No
Number of Normal Modes
Single-normal-mode Single-normal-mode
Default Normal Mode (ac)
Voltage Independent Voltage and Frequency Independent
Test Input Voltage (V rms)
120 120
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
120 120
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
8 26.9
Efficiency at 25% Load Min Config Lowest Dependency (ac)
98 88.8
Efficiency at 50% Load Min Config Lowest Dependency (ac)
99 91.2
Efficiency at 75% Load Min Config Lowest Dependency (ac)
99 91.3
Efficiency at 100% Load Min Config Lowest Dependency (ac)
99 90.8
Weighted Efficiency Calc Min Config Lowest Dependency
99 91.1
Minimum Configuration Input Power Factor Lowest-Input Dependency
1 1
Efficiency (%)
99 91.1
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Integral Integral
Energy Storage System Removable to Another Room
No No
Energy Storage System Runtime at 100% Load (min.)
3 2
Energy Storage System Runtime at 50% Load (min.)
10 9
Energy Storage System Warranty (yrs)
2 2
Energy Storage System Information URL
N/A N/A
Network Connections Available
Serial Port,Other,USB Port Other,USB Port
Communication Protocols
HTTP,HTTPS,Modbus TCP,SNMP (v1, 2 or 3) None
Manufacturer Take Back Program
Yes Yes
Manufacturer Take Back Program URL
https://www.legrandav.com/ N/A
Model Web Page URL
https://www.legrandav.com/ N/A
Test Method Guidelines
N/A N/A
Date Qualified
April 29, 2022 November 14, 2023