Compare Schneider Electric – GVSUPS50KGS vs Schneider Electric – GVSUPS30KGS Specifications

GVSUPS50KGS GVSUPS30KGS
ENERGY STAR Partner
Schneider Electric Schneider Electric
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
Schneider Electric Schneider Electric
Model Name
Galaxy VS 50kW 480V w/o Batteries, Start-up 5x8 Galaxy VS 30kW 480V w/o Batteries, Start-up 5x8
Model Number
GVSUPS50KGS GVSUPS30KGS
Additional Model Information
,GVSUPS50KG, ,GVSUPS30KG,
Date Available On Market
March 18, 2019 March 18, 2019
Date Certified
July 27, 2018 July 27, 2018
Markets
United States, Canada United States, Canada
CB Model Identifier
ES_22220_GVSUPS50KGS_09122018183041_7041346 ES_22220_GVSUPS30KGS_09122018183153_7113994
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
GVSUPS20KGS GVSUPS20KGS
Active Output Power Rating Minimum Configuration (W)
20,000 20000
Apparent Output Power Rating Minimum Configuration (VA)
20,000 20000
Maximum Configuration Tested Model Number
GVSUPS100KGS GVSUPS100KGS
Active Output Power Rating Maximum Configuration (W)
100,000 100000
Topology (ac)
Multi-Mode Double Conversion Multi-Mode Double Conversion
Topology and Product Type Combined
ac - Other ac - Other
Application
Data Center Data Center
Rated Input Voltage (V rms)
480-480 480-480
Rated Input Frequency (Hz)
60-60 60-60
Rated Output Voltage (V)
480-480 480-480
Rated Output Frequency (Hz)
60-60 60-60
Rack Mountable
No No
Height (mm)
1,485 1485
Width (mm)
521 521
Depth (mm)
847 847
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage and Frequency Dependent,Voltage and Frequency Independent Voltage and Frequency Dependent,Voltage and Frequency Independent
Modular UPS
No No
Number of Normal Modes
Multiple-normal-mode Multiple-normal-mode
Default Normal Mode (ac)
Voltage and Frequency Independent Voltage and Frequency Independent
Test Input Voltage (V rms)
480 480
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
480 480
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
246 246.28
Total Input Power in W at 0% Load Min Config Highest Dependency (ac)
153 152.59
Efficiency at 25% Load Min Config Lowest Dependency (ac)
93 93.3
Efficiency at 25% Load Min Config Highest Dependency (ac)
97 96.9
Efficiency at 50% Load Min Config Lowest Dependency (ac)
96 95.5
Efficiency at 50% Load Min Config Highest Dependency (ac)
98 98.3
Efficiency at 75% Load Min Config Lowest Dependency (ac)
96 96.4
Efficiency at 75% Load Min Config Highest Dependency (ac)
99 98.7
Efficiency at 100% Load Min Config Lowest Dependency (ac)
97 96.8
Efficiency at 100% Load Min Config Highest Dependency (ac)
99 98.9
Weighted Efficiency Calc Min Config Lowest Dependency
95 95.2
Weighted Efficiency Calc Min Config Highest Dependency
98 98
Minimum Configuration Input Power Factor Lowest-Input Dependency
1 0.96
Minimum Configuration Input Power Factor Highest-Input Dependency
1 0.92
Total Input Power in W at 0% Load Max Config Lowest Dependency (ac)
0 0.428
Total Input Power in W at 0% Load Max Config Highest Dependency (ac)
0 0.228
Efficiency at 25% Load Max Config Lowest Dependency (ac)
96 96.2
Efficiency at 25% Load Max Config Highest Dependency (ac)
99 98.8
Efficiency at 50% Load Max Config Lowest Dependency (ac)
97 97.1
Efficiency at 50% Load Max Config Highest Dependency (ac)
99 99.2
Efficiency at 75% Load Max Config Lowest Dependency (ac)
97 97.2
Efficiency at 75% Load Max Config Highest Dependency (ac)
99 99.3
Efficiency at 100% Load Max Config Lowest Dependency (ac)
97 97.2
Efficiency at 100% Load Max Config Highest Dependency (ac)
99 99.4
Weighted Efficiency Calc Max Config Lowest Dependency
97 96.9
Weighted Efficiency Calc Max Config Highest Dependency
99 99.1
Maximum Configuration Input Power Factor Lowest-Input Dependency
1 0.99
Maximum Configuration Input Power Factor Highest-Input Dependency
1 0.99
Efficiency (%)
96 95.9
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Separate Enclosure Separate Enclosure
Energy Storage System Removable to Another Room
Yes Yes
Energy Storage System Runtime at 100% Load (min.)
N/A N/A
Energy Storage System Runtime at 50% Load (min.)
N/A N/A
Energy Storage System Warranty (yrs)
N/A N/A
Energy Storage System Information URL
0 0
Battery Recycling URL
http://www.apc.com/us/en/who-we-are/sustainability/recycling-options.jsp http://www.apc.com/us/en/who-we-are/sustainability/recycling-options.jsp
Network Connections Available
Serial Port,Ethernet Serial Port,Ethernet
Communication Protocols
Modbus TCP,HTTPS,Other,HTTP,SNMP (v1, 2 or 3),Modbus RTU Modbus TCP,HTTPS,Other,HTTP,SNMP (v1, 2 or 3),Modbus RTU
Communication Protocol Other
BACnet/IP BACnet/IP
Manufacturer Take Back Program
Yes Yes
Manufacturer Take Back Program URL
http://www.apc.com/us/en/who-we-are/sustainability/recycling-options.jsp http://www.apc.com/us/en/who-we-are/sustainability/recycling-options.jsp
Model Web Page URL
http://www.apc.com/shop/us/en/products/P-GVSUPS50KGS http://www.apc.com/shop/us/en/products/P-GVSUPS30KGS
Test Method Guidelines
0 0
Date Qualified
July 27, 2018 July 27, 2018

Compare Schneider Electric - GVSUPS50KGS With Other 59 Models

Scroll to Top