ENERGY STAR Partner |
Schneider Electric |
Schneider Electric |
Product Category |
Uninterruptible Power Supplies |
Uninterruptible Power Supplies |
Type |
Ac-output UPS |
Ac-output UPS |
Brand Name |
Schneider Electric |
Schneider Electric |
Model Name |
Galaxy VS 50kW 480V w/o Batteries, Start-up 5x8 |
APC Smart-UPS Modular Ultra 5kW Scalable to 20kWN+1 Redundant, Rackmount, 120+208/240V |
Model Number |
GVSUPS50KGS |
SRYL5K20RMXLT |
Additional Model Information |
,GVSUPS50KG, |
APC Smart-UPS Modular Ultra 5kW Scalable to 20kW N+1 Redundant, Rackmount, 120+208/240V Factory Serviced,SRYL5K20RMXLTW,; Std Exch APC Smart-UPS Modular Ultra 5kW Scalable to 20kW N+1 Redundant, Rackmount, 120+208/240V,SRYL5K20RMXLTQ, |
Date Available On Market |
March 18, 2019 |
October 3, 2022 |
Date Certified |
July 27, 2018 |
August 9, 2022 |
Markets |
United States, Canada |
United States, Canada |
CB Model Identifier |
ES_22220_GVSUPS50KGS_09122018183041_7041346 |
ES_22220_SRYL5K20RMXLT_080220221355570_7844612 |
Meets ENERGY STAR Most Efficient 2024 Criteria |
No |
No |
Power Conversion Mechanism |
Static |
Static |
Minimum Configuration Tested Model Number |
GVSUPS20KGS |
SRYL5K20RMXLT |
Active Output Power Rating Minimum Configuration (W) |
20,000 |
5000 |
Apparent Output Power Rating Minimum Configuration (VA) |
20,000 |
5000 |
Maximum Configuration Tested Model Number |
GVSUPS100KGS |
SRYL20K20RMXLT |
Active Output Power Rating Maximum Configuration (W) |
100,000 |
20000 |
Topology (ac) |
Multi-Mode Double Conversion |
Multi-Mode Double Conversion |
Topology and Product Type Combined |
ac - Other |
ac - Other |
Application |
Data Center |
Commercial |
Rated Input Voltage (V rms) |
480-480 |
208-240 |
Rated Input Frequency (Hz) |
60-60 |
50-60 |
Rated Output Voltage (V) |
480-480 |
208-240 |
Rated Output Frequency (Hz) |
60-60 |
50-60 |
Rack Mountable |
No |
No |
Height (mm) |
1,485 |
390 |
Width (mm) |
521 |
440 |
Depth (mm) |
847 |
700 |
Normal Mode(s) Input Dependency Characteristic (ac) |
Voltage and Frequency Dependent,Voltage and Frequency Independent |
Voltage and Frequency Independent,Voltage and Frequency Dependent |
Modular UPS |
No |
Yes |
Number of Normal Modes |
Multiple-normal-mode |
Multiple-normal-mode |
Default Normal Mode (ac) |
Voltage and Frequency Independent |
Voltage and Frequency Independent |
Test Input Voltage (V rms) |
480 |
240 |
Test Input Frequency (Hz) |
60 |
60 |
Test Output Voltage (V) |
480 |
240 |
Test Output Frequency (Hz) |
60 |
60 |
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac) |
246 |
72.4 |
Total Input Power in W at 0% Load Min Config Highest Dependency (ac) |
153 |
77.6 |
Efficiency at 25% Load Min Config Lowest Dependency (ac) |
93 |
92.9 |
Efficiency at 25% Load Min Config Highest Dependency (ac) |
97 |
93.5 |
Efficiency at 50% Load Min Config Lowest Dependency (ac) |
96 |
94.9 |
Efficiency at 50% Load Min Config Highest Dependency (ac) |
98 |
96.4 |
Efficiency at 75% Load Min Config Lowest Dependency (ac) |
96 |
95.1 |
Efficiency at 75% Load Min Config Highest Dependency (ac) |
99 |
97.4 |
Efficiency at 100% Load Min Config Lowest Dependency (ac) |
97 |
94.7 |
Efficiency at 100% Load Min Config Highest Dependency (ac) |
99 |
97.9 |
Weighted Efficiency Calc Min Config Lowest Dependency |
95 |
94.9 |
Weighted Efficiency Calc Min Config Highest Dependency |
98 |
97.2 |
Minimum Configuration Input Power Factor Lowest-Input Dependency |
1 |
1 |
Minimum Configuration Input Power Factor Highest-Input Dependency |
1 |
1 |
Total Input Power in W at 0% Load Max Config Lowest Dependency (ac) |
0 |
194.4 |
Total Input Power in W at 0% Load Max Config Highest Dependency (ac) |
0 |
216.8 |
Efficiency at 25% Load Max Config Lowest Dependency (ac) |
96 |
94.2 |
Efficiency at 25% Load Max Config Highest Dependency (ac) |
99 |
95.2 |
Efficiency at 50% Load Max Config Lowest Dependency (ac) |
97 |
95.4 |
Efficiency at 50% Load Max Config Highest Dependency (ac) |
99 |
97.2 |
Efficiency at 75% Load Max Config Lowest Dependency (ac) |
97 |
95.4 |
Efficiency at 75% Load Max Config Highest Dependency (ac) |
99 |
97.8 |
Efficiency at 100% Load Max Config Lowest Dependency (ac) |
97 |
94.8 |
Efficiency at 100% Load Max Config Highest Dependency (ac) |
99 |
98.1 |
Weighted Efficiency Calc Max Config Lowest Dependency |
97 |
95.1 |
Weighted Efficiency Calc Max Config Highest Dependency |
99 |
96.9 |
Maximum Configuration Input Power Factor Lowest-Input Dependency |
1 |
1 |
Maximum Configuration Input Power Factor Highest-Input Dependency |
1 |
1 |
Efficiency (%) |
96 |
94.9 |
Modular UPS Module Tested Model Number |
N/A |
SRYL5KPMT |
Energy Storage Mechanism |
Battery |
Battery |
Energy Storage System Technology |
Valve Regulated Lead-acid Battery |
Lithium-ion Battery |
Energy Storage System Configuration |
Separate Enclosure |
Integral |
Energy Storage System Removable to Another Room |
Yes |
No |
Energy Storage System Runtime at 100% Load (min.) |
N/A |
5 |
Energy Storage System Runtime at 50% Load (min.) |
N/A |
12 |
Energy Storage System Warranty (yrs) |
N/A |
5 |
Energy Storage System Information URL |
0 |
https://www.apc.com/us/en/product/SRYLBM |
Battery Recycling URL |
http://www.apc.com/us/en/who-we-are/sustainability/recycling-options.jsp |
https://www.apc.com/us/en/who-we-are/sustainability/recycling-options.jsp |
Network Connections Available |
Serial Port,Ethernet |
Serial Port,Ethernet |
Communication Protocols |
Modbus TCP,HTTPS,Other,HTTP,SNMP (v1, 2 or 3),Modbus RTU |
HTTP,HTTPS,Modbus TCP,SNMP (v1, 2 or 3),Modbus RTU |
Communication Protocol Other |
BACnet/IP |
N/A |
Manufacturer Take Back Program |
Yes |
Yes |
Manufacturer Take Back Program URL |
http://www.apc.com/us/en/who-we-are/sustainability/recycling-options.jsp |
https://www.apc.com/us/en/who-we-are/sustainability/recycling-options.jsp |
Model Web Page URL |
http://www.apc.com/shop/us/en/products/P-GVSUPS50KGS |
https://www.apc.com/us/en/product/SRYL5K20RMXLT |
Test Method Guidelines |
0 |
https://www.apc.com/us/en/who-we-are/sustainability/ |
Date Qualified |
July 27, 2018 |
August 9, 2022 |