Compare Tripp Lite – ECO850LCD vs Tripp Lite – SUINT2200LCD2U Specifications

ECO850LCD SUINT2200LCD2U
ENERGY STAR Partner
Eaton Corporation Eaton Corporation
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
Tripp Lite Tripp Lite
Model Name
AG-0316 AGPS7958
Model Number
ECO850LCD SUINT2200LCD2U
Date Available On Market
December 21, 2018 November 25, 2015
Date Certified
January 3, 2019 November 9, 2015
Markets
United States, Canada United States, Canada
CB Model Identifier
ES_1097458_ECO850LCD_01302019213236_2562438 ES_1097458_SUINT2200LCD2U_04262019110602_9681853
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
AG-0316 AGPS7958
Active Output Power Rating Minimum Configuration (W)
425 1980
Apparent Output Power Rating Minimum Configuration (VA)
850 2200
Topology (ac)
Passive Standby Multi-Mode Double Conversion
Topology and Product Type Combined
Alternating Current (ac) - Offline (VFD) ac - Other
Application
Commercial,Consumer Commercial,Consumer
Rated Input Voltage (V rms)
120-120 200-240
Rated Input Frequency (Hz)
50-60 50-60
Rated Output Voltage (V)
120-120 200-240
Rated Output Frequency (Hz)
50-60 50-60
Rack Mountable
No Yes
Height (mm)
85 88
Width (mm)
130 438
Depth (mm)
320 496
Total Number of Outlets
12 9
Number of Battery Backup and Surge Protected Outlets
6 9
Number of Surge Protected Only Outlets
6 0
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage and Frequency Dependent Voltage and Frequency Dependent,Voltage and Frequency Independent
Modular UPS
No No
Number of Normal Modes
Single-normal-mode Multiple-normal-mode
Default Normal Mode (ac)
Voltage and Frequency Dependent Voltage and Frequency Dependent
Test Input Voltage (V rms)
120 240
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
120 240
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
0 0.481
Efficiency at 25% Load Min Config Lowest Dependency (ac)
98 89.2
Efficiency at 50% Load Min Config Lowest Dependency (ac)
99 92.6
Efficiency at 75% Load Min Config Lowest Dependency (ac)
99 93.5
Efficiency at 100% Load Min Config Lowest Dependency (ac)
99 93.8
Weighted Efficiency Calc Min Config Lowest Dependency
99 93.3
Minimum Configuration Input Power Factor Lowest-Input Dependency
1 0.99
Efficiency (%)
99 94.3
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Integral Integral
Energy Storage System Removable to Another Room
No No
Energy Storage System Runtime at 100% Load (min.)
2 4
Energy Storage System Runtime at 50% Load (min.)
9 12
Energy Storage System Warranty (yrs)
3 3
Energy Storage System Information URL
N/A N/A
Battery Recycling URL
http://www.tripplite.com/en/support/recycling-program.cfm http://www.tripplite.com/en/support/recycling-program.cfm
Network Connections Available
USB Port,Ethernet Serial Port,USB Port,Ethernet
Communication Protocols
None None
Manufacturer Take Back Program
Yes Yes
Manufacturer Take Back Program URL
http://www.tripplite.com/en/support/recycling-program.cfm http://www.tripplite.com/en/support/recycling-program.cfm
Model Web Page URL
https://www.tripplite.com/eco-series-120v-850va-425w-energy-saving-standby-ups-usb-lcd-display-12-outlets~ECO850LCD https://www.tripplite.com/smartonline-208-230v-2.2kva-1.98kw-double-conversion-ups-2u-extended-run-snmp-card-option-lcd-usb-db9-energy-star~SUINT2200LCD2U
Test Method Guidelines
N/A N/A
Date Qualified
January 3, 2019 November 9, 2015

Compare Tripp Lite - ECO850LCD With Other 87 Models