ENERGY STAR Partner |
Vertiv Corporation |
Vertiv Corporation |
Product Category |
Uninterruptible Power Supplies |
Uninterruptible Power Supplies |
Type |
Ac-output UPS |
Ac-output UPS |
Brand Name |
Vertiv |
Vertiv |
Model Name |
Liebert EXS |
Liebert ITA2 20kVA |
Model Number |
EXS 0040kTH16FN01000 |
ITA2-20KRT208C |
Additional Model Information |
Liebert EXS F2 series,EXS 0030kTH16FN01000, |
N/A |
Date Available On Market |
May 1, 2018 |
April 30, 2024 |
Date Certified |
August 1, 2018 |
May 7, 2024 |
Markets |
United States, Switzerland, Taiwan, Japan, Canada |
United States, Canada |
CB Model Identifier |
ES_1097807_EXS 0040kTH16FN01000_08022018105124_7084359 |
ES_1097807_ITA2-20KRT208C_050920241156894_8143789 |
Meets ENERGY STAR Most Efficient 2024 Criteria |
No |
No |
Power Conversion Mechanism |
Static |
Static |
Minimum Configuration Tested Model Number |
EXS 0040kTH16FN01000 |
1 |
Active Output Power Rating Minimum Configuration (W) |
40,000 |
20000 |
Apparent Output Power Rating Minimum Configuration (VA) |
40,000 |
20000 |
Topology (ac) |
Multi-Mode Double Conversion |
Multi-Mode Double Conversion |
Topology and Product Type Combined |
ac - Other |
ac - Other |
Application |
Commercial,Consumer,Data Center |
Data Center,Consumer,Commercial |
Rated Input Voltage (V rms) |
380-415 |
208-220 |
Rated Input Frequency (Hz) |
50-60 |
50-60 |
Rated Output Voltage (V) |
380-415 |
208-220 |
Rated Output Frequency (Hz) |
50-60 |
50-60 |
Rack Mountable |
No |
No |
Height (mm) |
1,600 |
130 |
Width (mm) |
440 |
430 |
Depth (mm) |
749 |
590 |
Normal Mode(s) Input Dependency Characteristic (ac) |
Voltage and Frequency Dependent,Voltage and Frequency Independent |
Voltage and Frequency Independent,Voltage and Frequency Dependent |
Modular UPS |
No |
Yes |
Number of Normal Modes |
Multiple-normal-mode |
Multiple-normal-mode |
Default Normal Mode (ac) |
Voltage and Frequency Independent |
Voltage and Frequency Dependent |
Test Input Voltage (V rms) |
415 |
208 |
Test Input Frequency (Hz) |
60 |
60 |
Test Output Voltage (V) |
415 |
208 |
Test Output Frequency (Hz) |
60 |
60 |
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac) |
263 |
151.28 |
Efficiency at 25% Load Min Config Lowest Dependency (ac) |
95 |
93.6 |
Efficiency at 50% Load Min Config Lowest Dependency (ac) |
96 |
93.9 |
Efficiency at 75% Load Min Config Lowest Dependency (ac) |
96 |
93.4 |
Efficiency at 100% Load Min Config Lowest Dependency (ac) |
95 |
92.6 |
Weighted Efficiency Calc Min Config Lowest Dependency |
96 |
93.7 |
Minimum Configuration Input Power Factor Lowest-Input Dependency |
1 |
0.99 |
Efficiency (%) |
96 |
94.7 |
Modular UPS Module Tested Model Number |
N/A |
N/A |
Energy Storage Mechanism |
Battery |
Battery |
Energy Storage System Technology |
Valve Regulated Lead-acid Battery |
Valve Regulated Lead-acid Battery |
Energy Storage System Configuration |
Separate Enclosure |
Integral |
Energy Storage System Removable to Another Room |
No |
No |
Energy Storage System Runtime at 100% Load (min.) |
10 |
5 |
Energy Storage System Runtime at 50% Load (min.) |
20 |
15 |
Energy Storage System Warranty (yrs) |
1 |
1 |
Energy Storage System Information URL |
http://www.enersys.com/ http://www.eastpennunigy.com/ |
http://www.enersys.com, http://www.eastpennunigy.com/ |
Network Connections Available |
None |
USB Port |
Communication Protocols |
Other |
Other |
Manufacturer Take Back Program |
No |
No |
Model Web Page URL |
https://www.vertivco.com/en-us/products-catalog/critical-power/uninterruptible-power-supplies-ups/ |
https://www.vertivco.com/en-us/products-catalog/critical-power/uninterruptible-power-supplies-ups/ |
Test Method Guidelines |
N/A |
N/A |
Date Qualified |
August 1, 2018 |
May 7, 2024 |