Compare Vertiv – EXS 0060kTK16FN01000 vs Vertiv – PST5-500MT120 Specifications

EXS 0060kTK16FN01000 PST5-500MT120
ENERGY STAR Partner
Vertiv Corporation Vertiv Corporation
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
Vertiv Vertiv
Model Name
Liebert EXS Fr3 series PST5-500MT120
Model Number
EXS 0060kTK16FN01000 PST5-500MT120
Date Available On Market
September 1, 2018 May 1, 2019
Date Certified
August 17, 2018 April 3, 2019
Markets
United States, Switzerland, Taiwan, Japan, Canada United States, Canada
CB Model Identifier
ES_1097807_EXS 0060kTK16FN01000_08172018065600_8960926 ES_1097807_PST5-500MT120_04022019013057_2126416
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
EXS 0060kTK16FN01000 PST5-500MT120
Active Output Power Rating Minimum Configuration (W)
60,000 300
Apparent Output Power Rating Minimum Configuration (VA)
60,000 500
Topology (ac)
Multi-Mode Double Conversion Passive Standby
Topology and Product Type Combined
ac - Other Alternating Current (ac) - Offline (VFD)
Application
Commercial,Consumer,Data Center Data Center,Consumer,Commercial
Rated Input Voltage (V rms)
380-415 120-120
Rated Input Frequency (Hz)
50-60 50-60
Rated Output Voltage (V)
380-415 120-120
Rated Output Frequency (Hz)
50-60 50-60
Rack Mountable
No No
Height (mm)
1,600 97
Width (mm)
600 158
Depth (mm)
850 305
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage and Frequency Dependent,Voltage and Frequency Independent Voltage and Frequency Dependent
Modular UPS
No No
Number of Normal Modes
Multiple-normal-mode Single-normal-mode
Default Normal Mode (ac)
Voltage and Frequency Independent Voltage and Frequency Dependent
Test Input Voltage (V rms)
415 120
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
415 120
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
575 N/A
Efficiency at 25% Load Min Config Lowest Dependency (ac)
94 97.1
Efficiency at 50% Load Min Config Lowest Dependency (ac)
96 98.2
Efficiency at 75% Load Min Config Lowest Dependency (ac)
96 98.5
Efficiency at 100% Load Min Config Lowest Dependency (ac)
96 98.6
Weighted Efficiency Calc Min Config Lowest Dependency
95 98.1
Minimum Configuration Input Power Factor Lowest-Input Dependency
1 1
Efficiency (%)
95 98.1
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Separate Enclosure Integral
Energy Storage System Removable to Another Room
No N/A
Energy Storage System Runtime at 100% Load (min.)
10 3
Energy Storage System Runtime at 50% Load (min.)
20 9
Energy Storage System Warranty (yrs)
1 1
Energy Storage System Information URL
http://www.enersys.com/ http://www.eastpennunigy.com/ https://www.vertiv.com/en-us/products-catalog/critical-power/uninterruptible-power-supplies-ups/liebert-pst5-ups/
Network Connections Available
None USB Port
Communication Protocols
Other None
Manufacturer Take Back Program
No No
Model Web Page URL
https://www.vertivco.com/en-us/products-catalog/critical-power/uninterruptible-power-supplies-ups/ https://www.vertiv.com/en-us/products-catalog/critical-power/uninterruptible-power-supplies-ups/liebert-pst5-ups/
Test Method Guidelines
N/A N/A
Date Qualified
August 17, 2018 April 3, 2019