Compare Vertiv – GXE-06k00TL1102C00 vs Vertiv – EXS 0020kTH1AFN01000 Specifications

GXE-06k00TL1102C00 EXS 0020kTH1AFN01000
ENERGY STAR Partner
Vertiv Corporation Vertiv Corporation
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
Vertiv Vertiv
Model Name
GXE-06k00TL1102C00 Liebert EXS
Model Number
GXE-06k00TL1102C00 EXS 0020kTH1AFN01000
Additional Model Information
GXE-06k00TE1102C00,GXE-06k00TE1102C00,; GXE-06k00TE1102P00,GXE-06k00TE1102P00,; GXE-06k00TL1102P00,GXE-06k00TL1102P00, Liebert EXS,EXS 0010kTH1AFN01000,; Liebert EXS,EXS 0010kTH1AFN02000,; Liebert EXS,EXS 0015kTH1AFN01000,; Liebert EXS,EXS 0015kTH1AFN02000,; Liebert EXS,EXS 0020kTH1AFN02000,
Date Available On Market
December 1, 2018 October 19, 2017
Date Certified
November 2, 2018 January 23, 2019
Markets
United States, Switzerland, Taiwan, Japan, Canada United States, Taiwan, Japan, Canada
CB Model Identifier
ES_1097807_GXE-06k00TL1102C00_11022018063403_0443792 ES_1097807_EXS 0020kTH1AFN01000_03272019031745_6665378
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
GXE-06k00TL1102C00 0020kTH1AFN01000
Active Output Power Rating Minimum Configuration (W)
5,400 20000
Apparent Output Power Rating Minimum Configuration (VA)
6,000 20000
Topology (ac)
Multi-Mode Double Conversion Multi-Mode Double Conversion
Topology and Product Type Combined
ac - Other ac - Other
Application
Commercial,Consumer,Data Center Commercial,Consumer,Data Center
Rated Input Voltage (V rms)
220-240 380-415
Rated Input Frequency (Hz)
50-60 50-60
Rated Output Voltage (V)
220-240 240-415
Rated Output Frequency (Hz)
50-60 50-60
Rack Mountable
Yes No
Height (mm)
350 1300
Width (mm)
160 335
Depth (mm)
400 650
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage and Frequency Dependent,Voltage and Frequency Independent Voltage and Frequency Dependent,Voltage and Frequency Independent
Modular UPS
No No
Number of Normal Modes
Multiple-normal-mode Multiple-normal-mode
Default Normal Mode (ac)
Voltage and Frequency Independent Voltage and Frequency Independent
Test Input Voltage (V rms)
240 415
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
240 415
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
30 97.49
Efficiency at 25% Load Min Config Lowest Dependency (ac)
95 95.1
Efficiency at 50% Load Min Config Lowest Dependency (ac)
96 96.1
Efficiency at 75% Load Min Config Lowest Dependency (ac)
96 96.1
Efficiency at 100% Load Min Config Lowest Dependency (ac)
95 95.8
Weighted Efficiency Calc Min Config Lowest Dependency
95 95.9
Minimum Configuration Input Power Factor Lowest-Input Dependency
1 0.99
Efficiency (%)
95 95.9
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Separate Enclosure Integral
Energy Storage System Removable to Another Room
No No
Energy Storage System Runtime at 100% Load (min.)
6 7
Energy Storage System Runtime at 50% Load (min.)
14 21
Energy Storage System Warranty (yrs)
2 1
Energy Storage System Information URL
http://www.enersys.com/ http://www.eastpennunigy.com/ N/A
Network Connections Available
USB Port,Ethernet Serial Port,Other,USB Port,Ethernet
Communication Protocols
Other Modbus TCP,HTTPS,Other,HTTP,SNMP (v1, 2 or 3),Modbus RTU
Manufacturer Take Back Program
No No
Model Web Page URL
https://www.vertivco.com/en-us/products-catalog/critical-power/uninterruptible-power-supplies-ups/ https://www.vertivco.com
Test Method Guidelines
N/A N/A
Date Qualified
November 2, 2018 January 23, 2019

Compare Vertiv - GXE-06k00TL1102C00 With Other 94 Models