Compare Vertiv – GXT5-2000LVRT2UXL vs Vertiv – EXS 0040kTH16FN01000 Specifications

GXT5-2000LVRT2UXL EXS 0040kTH16FN01000
ENERGY STAR Partner
Vertiv Corporation Vertiv Corporation
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
Vertiv Vertiv
Model Name
GXT5-2000LVRT2UXL Liebert EXS
Model Number
GXT5-2000LVRT2UXL EXS 0040kTH16FN01000
Additional Model Information
GXT5-2000LVRT2UXLB,GXT5-2000LVRT3UXLB, Liebert EXS F2 series,EXS 0030kTH16FN01000,
Date Available On Market
December 1, 2018 May 1, 2018
Date Certified
December 6, 2018 August 1, 2018
Markets
United States, Taiwan, Japan, Canada United States, Switzerland, Taiwan, Japan, Canada
CB Model Identifier
ES_1097807_GXT5-2000LVRT2UXL_12072018022221_9341777 ES_1097807_EXS 0040kTH16FN01000_08022018105124_7084359
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
GXT5-2000LVRT2UXL EXS 0040kTH16FN01000
Active Output Power Rating Minimum Configuration (W)
1,800 40000
Apparent Output Power Rating Minimum Configuration (VA)
2,000 40000
Topology (ac)
Multi-Mode Double Conversion Multi-Mode Double Conversion
Topology and Product Type Combined
ac - Other ac - Other
Application
Commercial,Consumer,Data Center Commercial,Consumer,Data Center
Rated Input Voltage (V rms)
110-125 380-415
Rated Input Frequency (Hz)
50-60 50-60
Rated Output Voltage (V)
110-125 380-415
Rated Output Frequency (Hz)
50-60 50-60
Rack Mountable
Yes No
Height (mm)
85 1600
Width (mm)
430 440
Depth (mm)
470 749
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage and Frequency Dependent,Voltage and Frequency Independent Voltage and Frequency Dependent,Voltage and Frequency Independent
Modular UPS
No No
Number of Normal Modes
Multiple-normal-mode Multiple-normal-mode
Default Normal Mode (ac)
Voltage and Frequency Independent Voltage and Frequency Independent
Test Input Voltage (V rms)
120 415
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
120 415
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
28 262.6
Efficiency at 25% Load Min Config Lowest Dependency (ac)
91 95.2
Efficiency at 50% Load Min Config Lowest Dependency (ac)
93 96.2
Efficiency at 75% Load Min Config Lowest Dependency (ac)
92 95.7
Efficiency at 100% Load Min Config Lowest Dependency (ac)
92 95.2
Weighted Efficiency Calc Min Config Lowest Dependency
93 95.8
Minimum Configuration Input Power Factor Lowest-Input Dependency
1 0.99
Efficiency (%)
93 95.8
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Separate Enclosure Separate Enclosure
Energy Storage System Removable to Another Room
No No
Energy Storage System Runtime at 100% Load (min.)
3 10
Energy Storage System Runtime at 50% Load (min.)
9 20
Energy Storage System Warranty (yrs)
2 1
Energy Storage System Information URL
http://www.enersys.com/ http://www.eastpennunigy.com/ http://www.enersys.com/ http://www.eastpennunigy.com/
Network Connections Available
USB Port,Ethernet None
Communication Protocols
Other Other
Manufacturer Take Back Program
No No
Model Web Page URL
https://www.vertivco.com/en-us/products-catalog/critical-power/uninterruptible-power-supplies-ups/ https://www.vertivco.com/en-us/products-catalog/critical-power/uninterruptible-power-supplies-ups/
Test Method Guidelines
N/A N/A
Date Qualified
December 6, 2018 August 1, 2018

Compare Vertiv - GXT5-2000LVRT2UXL With Other 94 Models