Compare Tripp Lite – INTERNET750U vs Tripp Lite – SU3000LCD2UHV Specifications

INTERNET750U SU3000LCD2UHV
ENERGY STAR Partner
Eaton Corporation Eaton Corporation
Product Category
Uninterruptible Power Supplies Uninterruptible Power Supplies
Type
Ac-output UPS Ac-output UPS
Brand Name
Tripp Lite Tripp Lite
Model Name
AG-0314 AGPS8296
Model Number
INTERNET750U SU3000LCD2UHV
Additional Model Information
AG-0390,BC800U, N/A
Date Available On Market
December 28, 2018 July 24, 2015
Date Certified
January 3, 2019 August 17, 2015
Markets
United States, Canada United States, Canada
CB Model Identifier
ES_1097458_INTERNET750U_11282018160442_2182782 ES_1097458_SU3000LCD2UHV_03112019114354_3621167
Meets ENERGY STAR Most Efficient 2024 Criteria
No No
Power Conversion Mechanism
Static Static
Minimum Configuration Tested Model Number
AG-0314 AGPS8296
Active Output Power Rating Minimum Configuration (W)
450 2700
Apparent Output Power Rating Minimum Configuration (VA)
750 2700
Topology (ac)
Passive Standby Multi-Mode Double Conversion
Topology and Product Type Combined
Alternating Current (ac) - Offline (VFD) ac - Other
Application
Commercial,Consumer Commercial,Consumer
Rated Input Voltage (V rms)
120-120 200-240
Rated Input Frequency (Hz)
50-60 50-60
Rated Output Voltage (V)
120-120 200-240
Rated Output Frequency (Hz)
50-60 50-60
Rack Mountable
No Yes
Height (mm)
85 88
Width (mm)
130 438
Depth (mm)
320 616
Total Number of Outlets
12 8
Number of Battery Backup and Surge Protected Outlets
6 8
Number of Surge Protected Only Outlets
6 0
Normal Mode(s) Input Dependency Characteristic (ac)
Voltage and Frequency Dependent Voltage and Frequency Dependent,Voltage and Frequency Independent
Modular UPS
No No
Number of Normal Modes
Single-normal-mode Multiple-normal-mode
Default Normal Mode (ac)
Voltage and Frequency Dependent Voltage and Frequency Dependent
Test Input Voltage (V rms)
120 240
Test Input Frequency (Hz)
60 60
Test Output Voltage (V)
120 240
Test Output Frequency (Hz)
60 60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)
0 0.616
Efficiency at 25% Load Min Config Lowest Dependency (ac)
99 88.8
Efficiency at 50% Load Min Config Lowest Dependency (ac)
99 91.9
Efficiency at 75% Load Min Config Lowest Dependency (ac)
100 92.7
Efficiency at 100% Load Min Config Lowest Dependency (ac)
100 92.7
Weighted Efficiency Calc Min Config Lowest Dependency
99 92.5
Minimum Configuration Input Power Factor Lowest-Input Dependency
1 1
Efficiency (%)
99 93.6
Modular UPS Module Tested Model Number
N/A N/A
Energy Storage Mechanism
Battery Battery
Energy Storage System Technology
Valve Regulated Lead-acid Battery Valve Regulated Lead-acid Battery
Energy Storage System Configuration
Integral Integral
Energy Storage System Removable to Another Room
No No
Energy Storage System Runtime at 100% Load (min.)
2 5
Energy Storage System Runtime at 50% Load (min.)
9 14
Energy Storage System Warranty (yrs)
3 3
Energy Storage System Information URL
N/A N/A
Battery Recycling URL
http://www.tripplite.com/en/support/recycling-program.cfm http://www.tripplite.com/en/support/recycling-program.cfm
Network Connections Available
USB Port Serial Port,USB Port,Ethernet
Communication Protocols
None None
Manufacturer Take Back Program
Yes Yes
Manufacturer Take Back Program URL
http://www.tripplite.com/en/support/recycling-program.cfm http://www.tripplite.com/en/support/recycling-program.cfm
Model Web Page URL
https://www.tripplite.com/internet-office-120v-750va-450w-standby-ups-ultra-compact-desktop-usb~INTERNET750U https://www.tripplite.com/smartonline-208-240v-3kva-2.7kw-double-conversion-ups-2u-extended-run-snmp-card-option-lcd-usb-db9-energy-star~SU3000LCD2UHV
Test Method Guidelines
N/A N/A
Date Qualified
January 3, 2019 August 17, 2015