S4K2U3000D by Emerson – Specifications

Introducing the Emerson SOLAHD S4K2U3000D, a state-of-the-art Ac-output UPS designed for the modern consumer.

This model, S4K2U3000D, is part of the ENERGY STAR certified products and is brought to you by Appleton Grp LLC d/b/a Appleton Group.

Key Features:

  • Date Available On Market: January 1, 2024
  • Date Certified: October 31, 2023
  • Markets: United States, Canada
  • CB Model Identifier: ES_1129526_S4K2U3000D_103120231742756_7362427
  • Meets ENERGY STAR Most Efficient 2024 Criteria: No
  • Application: Commercial

Available in United States, Canada markets, the Emerson SOLAHD S4K2U3000D is the perfect addition to any home, offering both performance and energy efficiency.

Release Date: January 1, 2024 Qualified Date: October 31, 2023

Don't miss out on this high-performance, energy-efficient Ac-output UPS.

Get yours today and enjoy the ultimate viewing experience!

Full Specifications of S4K2U3000D

ENERGY STAR PartnerAppleton Grp LLC d/b/a Appleton Group
Product CategoryUninterruptible Power Supplies
TypeAc-output UPS
Brand NameEmerson
Model NameSOLAHD S4K2U3000D
Model NumberS4K2U3000D
Date Available On MarketJanuary 1, 2024
Date CertifiedOctober 31, 2023
MarketsUnited States, Canada
CB Model IdentifierES_1129526_S4K2U3000D_103120231742756_7362427
Meets ENERGY STAR Most Efficient 2024 CriteriaNo
Power Conversion MechanismStatic
Minimum Configuration Tested Model NumberS4K2U3000D
Active Output Power Rating Minimum Configuration (W)2,700
Apparent Output Power Rating Minimum Configuration (VA)3,000
Topology (ac)Double Conversion
Topology and Product Type Combinedac - Double Conversion (VFI)
ApplicationCommercial
Rated Input Voltage (V rms)110-125
Rated Input Frequency (Hz)50-60
Rated Output Voltage (V)110-125
Rated Output Frequency (Hz)50-60
Rack MountableYes
Height (mm)85
Width (mm)430
Depth (mm)627
Normal Mode(s) Input Dependency Characteristic (ac)Voltage and Frequency Independent
Modular UPSNo
Number of Normal ModesSingle-normal-mode
Default Normal Mode (ac)Voltage and Frequency Independent
Test Input Voltage (V rms)120
Test Input Frequency (Hz)60
Test Output Voltage (V)120
Test Output Frequency (Hz)60
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac)43
Efficiency at 25% Load Min Config Lowest Dependency (ac)92
Efficiency at 50% Load Min Config Lowest Dependency (ac)94
Efficiency at 75% Load Min Config Lowest Dependency (ac)94
Efficiency at 100% Load Min Config Lowest Dependency (ac)93
Weighted Efficiency Calc Min Config Lowest Dependency94
Efficiency (%)94
Modular UPS Module Tested Model NumberN/A
Energy Storage MechanismBattery
Energy Storage System TechnologyValve Regulated Lead-acid Battery
Energy Storage System ConfigurationIntegral
Energy Storage System Removable to Another RoomNo
Energy Storage System Runtime at 100% Load (min.)4
Energy Storage System Runtime at 50% Load (min.)13
Energy Storage System Warranty (yrs)2
Energy Storage System Information URLwww.appleton.emerson.com/en-us/electrical-components-lighting/power-quality-distribution
Network Connections AvailableSerial Port,Other,Ethernet,USB Port
Communication ProtocolsHTTP,HTTPS,Other,Modbus TCP,SNMP (v1, 2 or 3),Modbus RTU
Manufacturer Take Back ProgramYes
Model Web Page URLhttps://www.appleton.emerson.com/en-us/electrical-components-lighting/power-quality-distribution
Test Method GuidelinesN/A
Date QualifiedOctober 31, 2023